A switch indicator

Ensure that there is not a short circuit in the wiring for the switch.

always reads “Closed”

Measure the resistance between the “A” and “B” terminals for the

 

appropriate indicator. If the switch is open, the resistance should

 

either be an open-circuit, if the indicator is configured as “No End

 

of Line Resistor”, or should measure 8 KΩ if the indicator is

 

configured as “End of Line Resistor”. If the switch is closed, the

 

resistance should be close to 0 Ω.

A switch indicator

Ensure that the configuration of the indicator matches the circuit

always reads “Error”

connected to it. Measure the resistance between the “A” and “B”

 

terminals for the appropriate indicator. If the switch is open, the

 

resistance should either be an open-circuit, if the indicator is

 

configured as “No End of Line Resistor”, or should measure 8 KΩ if

 

the indicator is configured as “End of Line Resistor”. If the switch

 

is closed, the resistance should be close to 0 Ω.

A switch indicator

Ensure that the switch is connected to the indicator terminals that

always reads “Open”

that there are no open circuits between the SIM100 and the switch.

 

Measure the resistance between the “A” and “B” terminals for the

 

appropriate indicator. If the switch is open, the resistance should

 

either be an open-circuit, if the indicator is configured as “No End

 

of Line Resistor”, or should measure 8 KΩ if the indicator is

 

configured as “End of Line Resistor”. If the switch is closed, the

 

resistance should be close to 0 Ω.