ELECTRICAL REQUIREMENTS

INSTALLATION

INSTRUCTIONS (CONTINUED)

ELECTRICAL REQUIREMENTS

It is the responsibility of the spa owner to ensure that all electrical connections are made in accor- dance with all electric codes in effect at the time of installation.

240 Volt:

All connections must be made in accordance with the wiring diagram found on the inside of the control box cover. Connections should be made with copper conductors only – aluminum wiring should not be used with this system. All conductors, circuit breakers, and/or fuses must be sized in accordance to the Total Amperage Load as specified:

Permanently connected

Rated 240V, 60Hz, 50A, three wires plus ground (6 AWG copper)

Fuse or circuit breaker size: 50 amp

This equipment is designed to operate on 60Hz Alternating Current only at a voltage of 240. Units to be operated at 240V must have all connections made by a qualified electrician in accordance with any electric codes in effect at the time of installation. All 240V units require a three wire plus ground (line 1, line 2, neutral, ground). Refer to the label at the terminal block.

A pressure wire connector is located on the exterior of the control box. If the installation includes a common bonding grid (reinforced concrete slab, ground plate beneath the spa, or any metal water pipe connection), this pressure wire connector should be bonded, with at least #8 AWG (8.42mm2, #6 in Canada) copper wire, to any metal ladder, water pipe, or other metal, within five feet of the spa.

120 Volt:

120V units must only be connected to a properly grounded, grounding type15 amp receptacle. 120V equipment is designed to operate on 60Hz Alternating current only at a voltage of 120, 12.5 amp. maximum load.

To Convert 120V to 240V

All connections must be made by a licensed electrician.

1.Disconnect from power and remove cord.

2.Move red wire (TB-1) to (TB-4) as indicated by gray area.

3.Move the Heater Mode selector (J23) on the Control Board from (20A) to (50A) position. Ground Fault Circuit Interrupters (GFCI), #8145, are available from your Dealer.