Low temperature burners - INDITHERM®

1 - 2.3 - 21 E - m - 7/08

Start-up instructions for INDITHERM® burners

Instructions provided by the company or individual responsible for the manufacture and/or overall installa- tion of a complete system incorporating MAXON burners take precedence over the installation and operat- ing instructions provided by MAXON. If any of the instructions provided by MAXON are in conflict with local codes or regulations, please contact MAXON before initial start-up of equipment.

Read the combustion system manual carefully before initiating the start-up and adjustment procedure.Verify that all of the equipment associated with and necessary to the safe operation of the burner system has been installed correctly, that all pre- commissioning checks have been carried out successfully and that all safety related aspects of the installation are properly addressed.

Initial adjustment and light-off should be undertaken only by a trained commissioning engineer.

„First firing or restart after shut-down

During first start-up of the burner, allow extended period at low firing range to minimize potential damage from accumulated and retained moisture in refractory burner block.

During cold starts, the temperature rise shall be limited – allow the burner to fire on low fire for some time to allow the parts to heat up slowly for maximum life.

„Safety interlocks

Guarantee that all the required safety locks as described in the applicable local codes or regulations, or supplementary safety blocks requested for safe operation of the overall installation, are working properly and resulting in a positive safety-lock of the burner. Do not bypass any of these safety interlocks, this will result in unsafe operation.

„Checks during and after start up

During and after start-up, check the integrity of the system. Check all bolted connections after first firing (first time on tempera- ture) and retighten if necessary.

„Purge

For safety reasons, it is required to purge the installation sufficiently long to ensure that all possible combustibles are evacu- ated before ignition. Refer to the applicable local codes and your specific application requirements to determine the purge time.

„Pilot ignition

Adjust pilot air flow and pilot gas regulator to correct set point before pilot ignition attempt.Turn adjustable orifice screw out (counter-clockwise) several turns from its fully seated position. Refine during lighting of the pilot to a yellow/blue flame and/or strongest stable flame signal.

„Main burner ignition

Adjust the main gas regulator at the correct set point before igniting the main burner. Ensure that the gas/air ratio valve is in the start position when lighting the main burner.

After ignition of main burner, allow some time on minimum capacity to allow the burner parts to heat up slowly.

„Burner adjustment

Once the main flame is ignited, adjust gas pressure to the burner to have the required combustion quality. Slowly increase capacity while observing the flame and measuring flue gas quality. Do not increase capacity too fast to avoid damage to burner parts or furnace due to excessive temperature gradient.

w w w . m a x o n c o r p . c o m

combustion systems for industry

MAXON reserves the right to alter specifications and data without prior notice. © 2008 Copyright Maxon Corporation. All rights reserved.

Page 16
Image 16
Maxon Telecom 850, 550, 700, 300, 1800, 1500, 1100 specifications Start-up instructions for Inditherm burners, 3 21 E m 7/08

1100, 100, 1500, 700, 550 specifications

Maxon Telecom 1800, 850, 700, 1500, 300 represents a series of advanced telecommunications infrastructure solutions that cater to diverse connectivity needs. With its robust features and modern technologies, Maxon Telecom is paving the way for enhanced communication in various sectors, including mobile networks, satellite services, and broadband applications.

One of the main features of the Maxon Telecom series is its multi-band capabilities. Supporting frequencies such as 1800 MHz, 850 MHz, and 700 MHz, these systems enable operators to provide seamless coverage and improved data speeds across urban and rural landscapes. The 1500 MHz band is particularly advantageous for applications requiring high-capacity data throughput, making it suitable for dense population areas. The inclusion of the 300 MHz band enhances the offering by facilitating broader network coverage, crucial for emerging IoT technologies.

In terms of technology, Maxon Telecom utilizes state-of-the-art amplification and filtering systems that enhance signal clarity and strength. This approach minimizes dropouts and provides a consistent user experience. The incorporation of advanced digital signal processing techniques allows for better handling of high-volume data traffic, ensuring that users can stay connected even during peak usage times.

The design characteristics of the Maxon Telecom systems focus on both reliability and efficiency. Built to withstand various environmental conditions, these units come with rugged enclosures that protect against heat, moisture, and dust. Moreover, energy-efficient components ensure that the systems consume less power while delivering high performance, aligning with global sustainability goals.

Scalability is another key trait of the Maxon Telecom series. Operators can easily integrate these systems into existing networks, allowing for seamless upgrades without significant infrastructure changes. This modular approach also enables customization based on specific regional requirements, ensuring that the solutions can adapt as technology evolves.

Overall, Maxon Telecom 1800, 850, 700, 1500, 300 stands out as a comprehensive communication solution suitable for today's digital landscape. Its blend of multi-band support, advanced technology, and robust design makes it an ideal choice for telecom operators aiming to enhance their service offerings and meet the ever-increasing demands for reliable connectivity. Through continuous innovation, Maxon Telecom is well-positioned to address the challenges of modern communication needs.