Low temperature burners - INDITHERM®
1 - 2.3 - 21 E - m - 7/08
Start-up instructions for INDITHERM® burners
Instructions provided by the company or individual responsible for the manufacture and/or overall installa- tion of a complete system incorporating MAXON burners take precedence over the installation and operat- ing instructions provided by MAXON. If any of the instructions provided by MAXON are in conflict with local codes or regulations, please contact MAXON before initial
Read the combustion system manual carefully before initiating the
Initial adjustment and
First firing or restart after shut-down
During first
During cold starts, the temperature rise shall be limited – allow the burner to fire on low fire for some time to allow the parts to heat up slowly for maximum life.
Safety interlocks
Guarantee that all the required safety locks as described in the applicable local codes or regulations, or supplementary safety blocks requested for safe operation of the overall installation, are working properly and resulting in a positive
Checks during and after start up
During and after
Purge
For safety reasons, it is required to purge the installation sufficiently long to ensure that all possible combustibles are evacu- ated before ignition. Refer to the applicable local codes and your specific application requirements to determine the purge time.
Pilot ignition
Adjust pilot air flow and pilot gas regulator to correct set point before pilot ignition attempt.Turn adjustable orifice screw out
Main burner ignition
Adjust the main gas regulator at the correct set point before igniting the main burner. Ensure that the gas/air ratio valve is in the start position when lighting the main burner.
After ignition of main burner, allow some time on minimum capacity to allow the burner parts to heat up slowly.
Burner adjustment
Once the main flame is ignited, adjust gas pressure to the burner to have the required combustion quality. Slowly increase capacity while observing the flame and measuring flue gas quality. Do not increase capacity too fast to avoid damage to burner parts or furnace due to excessive temperature gradient.