2. Installation
Module 425 mm deep
Installation against a wall
Caution: during handling, make sure the module does not fall over.
25 |
|
| 26 |
≥ | 400 mm |
1250 |
|
1685,5 |
|
| ≥ 720 mm |
| 23 |
| 24 |
| 23 |
| 24 |
| 23 |
Rear of module | |
69.5 | 69.5 |
| 1076 |
67 | 67 |
276 |
|
82 | 82 |
Front of module | |
Page 10 - 34020201EN/AB |
|
1.Turn to horizontal position the two brackets 25 at the back used to secure the module (see figure).
2.Install the rear base panel 23 (not mandatory).
3.Position the module.
4.Level the module using the adjustable feet 24 .
5.Attach the module to the wall using the two rear brackets.
6.Install the base panels 23 on the sides and front.
7.Remove the bracket 26 on the top of the module (used only for
Connection cables run under the false floor or in a trough.
Important:
At least 400 mm of free space is required above the module to ensure correct ventilation.
At least 720 mm of free space is required in front to open the doors.
Footprint of module
Force exerted on the floor by the four feet: ◗28 kg/cm2.