6. Appendices

Card MCM (general status and measurements)

The variables entered in registers 1 to 74 are whole numbers read on 16 bits.

The variables entered in registers 1 to 29 are also accessible in “floating” format on 32 bits (registers 257 to 314 in the “Float.” column of the table). The “floating” variables are read only.

Multiply each value in whole number format by the coefficient indicated in the “Coeff.” column of the table.

# Bit

Float.

R/W

NV

Coeff.

Description

1

257/258

R/W

NV

0.1

Energy consumed in kWh (least significant bit of the word)*

2

259/260

R/W

NV

6553.6

Energy consumed in kWh (most significant bit of the word)*

3

261/262

R

 

0.1

Total active power in kW

4

263/264

R

 

0.1

Total reactive power in kVAR

5

265/266

R

 

0.1

Total apparent power in kVA

6

267/268

R

 

0.0001

Total power factor

7

269/270

R

 

0.01

Average of the phase-to-phase voltages in the 3 phases in V

8

271/272

R

 

0.01

Average of the phase-to-neutral voltages in the 3 phases in V

9

273/274

R

 

0.1

Average of the current in the 3 phases in A

10

275/276

R

 

0.01

Frequency in Hz

11

277/278

R

 

0.1

Active power for phase A in kW

12

279/280

R

 

0.1

Active power for phase B in kW

13

281/282

R

 

0.1

Active power for phase C in kW

14

283/284

R

 

0.0001

Power factor for phase A

15

285/286

R

 

0.0001

Power factor for phase B

16

287/288

R

 

0.0001

Power factor for phase C

17

289/290

R

 

0.01

Voltage between phase A and B in V

18

291/292

R

 

0.01

Voltage between phase B and C in V

19

293/294

R

 

0.01

Voltage between phase C and A in V

20

295/296

R

 

0.01

Voltage between phase A and the neutral in V

21

297/298

R

 

0.01

Voltage between phase B and the neutral in V

22

299/300

R

 

0.01

Voltage between phase C and the neutral in V

23

301/302

R

 

0.1

Current in phase A in A

24

303/304

R

 

0.1

Current in phase B in A

25

305/306

R

 

0.1

Current in phase C in A

26

307/308

R

 

0.1

Neutral current in A

27

309/310

R/W

 

0.1

Average total active power in kW*

28

311/312

R/W

 

0.1

Minimum total active power in kW*

29

313/314

R/W

 

0.1

Maximum total active power in kW*

30 to 36

 

R/W

NV

 

Reserved for MGE UPS SYSTEMS

37

 

R/W

NV

 

Alarms

0

 

 

 

 

Stored overload alarms (bit set to 1). Reset by setting bit to 0.

1 to 3

 

 

 

 

Unused bits (set to 0)

4

 

 

 

 

Stored overvoltage alarms (bit set to 1). Reset by setting bit to 0.

5 to 15

 

 

 

Unused bits (set to 0)

38 to 42

 

R/W

NV

 

Reserved for MGE UPS SYSTEMS

43 to 48

 

R

 

 

Reserved for MGE UPS SYSTEMS

49

 

R

NV

 

Alarms

0

 

 

 

 

Non-stored overload alarms (bit set to 1).

1 to 3

 

 

 

 

Unused bits (set to 0)

4

 

 

 

 

Non-stored overvoltage alarms (bit set to 1).

5 to 15

 

 

 

Unused bits (set to 0)

50 to 74

 

 

 

 

Reserved for MGE UPS SYSTEMS

*: Values valid since the last reset. Reset is carried out by writing a whole number value.

34020201EN/AB - Page 31

Page 31
Image 31
MGE UPS Systems 250A user manual Card MCM general status and measurements, # Bit Float Coeff Description

250A specifications

MGE UPS Systems has garnered a reputation for delivering high-quality power protection solutions, and the 250A model stands out as an excellent choice for businesses seeking reliable uninterruptible power supply (UPS) systems. This particular model is designed to handle critical loads while ensuring continuous power availability and safeguarding equipment against power disturbances.

One of the main features of the MGE UPS Systems 250A is its robust power capacity. It can efficiently supply power to critical devices, making it suitable for a range of applications including data centers, telecommunication networks, and industrial environments. The 250A offers a highly scalable solution, allowing businesses to expand their power needs as they grow.

In terms of technology, the MGE UPS Systems 250A utilizes advanced double-conversion technology, which converts incoming AC power to DC and then back to AC. This process ensures that the connected equipment receives a consistent and clean sine wave output, free from fluctuations and disturbances. The UPS is equipped with high-efficiency operation modes, including Eco-mode, which help reduce energy consumption and operational costs while maintaining optimal performance.

Another notable characteristic of the 250A is its versatility in connectivity and integration. It features a comprehensive range of communication ports, enabling seamless integration with existing infrastructures. The UPS can be monitored and managed remotely, allowing for real-time insights into the power status and performance metrics. This level of monitoring is crucial for ensuring optimal operation and for preemptively addressing potential issues.

Moreover, MGE UPS Systems has placed a strong emphasis on user-friendly design in the 250A model. The intuitive interface and clear display make it easy for operators to navigate through settings and configurations. Additionally, the modular design of the UPS allows for easy maintenance and upgrades, minimizing downtime and optimizing service efficiency.

To enhance its reliability, the MGE UPS Systems 250A comes with multiple safety features, including overload protection, short circuit protection, and temperature monitoring. These safeguards ensure that the system operates within safe parameters, reducing the risk of damage to both the UPS and connected equipment.

In summary, the MGE UPS Systems 250A is a powerful and versatile solution for businesses requiring reliable power protection. With its advanced technology, energy-efficient design, and user-friendly features, it meets the demands of modern power requirements while ensuring seamless operation and equipment safety.