"11" - battery circuit breaker in "off" position:

indicates that the battery circuit is open (battery circuit breaker 4 is in "off" position). The load is no longer protected because battery power is no longer available in the event of an AC input power failure. In the case of the "battery-free frequency converter" option, it is normal for the "11" message to remain on;

"12" - check battery: indicates that the battery should be checked (see Battery maintenance in the Maintenance and servicing section);

"13" - low battery shutdown warning: indicates that battery power will end after a user-set time period. The user must take the required measures to secure the load (load shedding, file saving and system shutdown, etc.);

"14" - end of battery power;

"15" - battery fault: indicates a problem with the battery (see "battery maintenance" in the "maintenance and servicing" section;

"16" - ambient T° fault: this display indicates that the ambient temperature is outside the tolerance range (<0°C or > 40°C);

"17" - battery periodic test: this message indicates that the battery is in the process of being checked;

"18" - battery manual test: this message indicates that the battery is in the process of being completely discharged in order to update the battery monitoring parameters;

"21" - inverter fault: indicates a fault in the inverter module 7 ; contact the after-sales support department;

"22" - inverter overtemperature: indicates overheating inside the UPS; check that the Comet ventilation system is working and that the ambient temperature is within tolerances (see "appendices");

"25" - inverter overload: indicates an overload when the load is being supplied via the inverter. Reduce the load;

"31" - Mains 2 voltage outside tolerance range: this display indicates that

the Mains 2 power supply voltage of the "static bypass" 3 is outside the tolerance range;

7.2

Comet installation and user manual: E-6761200XT/FA

Merlin Gerin by MGE UPS SYSTEMS

Page 32
Image 32
MGE UPS Systems Comet TM 5 - 30 kVA user manual Battery circuit breaker in off position, End of battery power

Comet TM 5 - 30 kVA specifications

MGE UPS Systems Comet TM 5 - 30 kVA is a reliable and efficient uninterruptible power supply (UPS) designed to ensure the smooth operation of critical systems in various applications. This UPS is particularly suited for data centers, telecommunications, and industrial environments that require high availability and robust power protection.

One of the main features of the Comet TM series is its modular design, which allows users to scale the UPS capacity as needed. This flexibility is crucial for businesses that anticipate growth or fluctuating power requirements. The UPS is available in a range of capacities, from 5 kVA to 30 kVA, allowing for tailored solutions that fit specific power needs.

The Comet TM is equipped with advanced double conversion technology, which provides clean and reliable power, isolating the connected equipment from input voltage disturbances. This technology ensures that any fluctuations in the mains supply, such as voltage sags or surges, do not affect the operation of sensitive electronic devices. Additionally, this UPS features a wide input voltage range that contributes to improved efficiency and reduced energy consumption.

An impressive aspect of the Comet TM is its high-efficiency mode, which optimizes energy consumption while maintaining power quality. This mode reduces operating costs and contributes to lower carbon footprints, making it an environmentally friendly choice. Furthermore, the UPS incorporates intelligent battery management systems, which enhance battery performance and extend their lifespan. This is essential in minimizing downtime and ensuring that backup power is readily available when needed.

The user-friendly interface of the Comet TM allows for easy monitoring and management of the system. With graphical displays and comprehensive alarms, users can promptly identify potential issues and take corrective actions. Remote management capabilities are also built into the system, enabling users to monitor and control the UPS remotely, which is particularly beneficial for businesses that operate across multiple locations.

In summary, the MGE UPS Systems Comet TM 5 - 30 kVA is designed for organizations that need reliable power protection and high efficiency. With its modular scalability, advanced double conversion technology, high-efficiency mode, intelligent battery management, and user-friendly interface, the Comet TM series stands out as a robust solution for critical power applications. Its combination of features ensures that businesses can maintain uninterrupted operations while benefiting from cost savings and a reduced environmental impact.