"32" - phase shift outside tolerance range: this display indicates that the

phase between the Mains 2 power supply of the "static bypass" 3 and the "inverter module" 7 is outside the tolerance range;

"33" - phase sequence fault: informs the user that the phase sequence of the three-phase power supply is incorrect;

"34" - frequency of Mains 2 power supply to "static bypass" 3 outside tolerances: the output inverter voltage is no more synchronised with Mains 2. load transfers may be carried out using the following procedure: press, for 3 seconds, simultaneously the security button 26 and:

the green "inverter on" button 22 to force transfer of the load to the inverter

7. Transfer results in a 0.5 second break in the supply of power to the load,

the grey "inverter off" button 23 to force transfer of the load to the "static bypass" 3 . Transfer results in a 0.5 second break in the supply of power to the load;

"35" - "static bypass" overload: indicates an overload when the load is being supplied via the "static bypass". Reduce the load;

"37" - Mains 1 voltage outside tolerance range: this display indicates that

the voltage of the Mains 1 power supply of the "rectifier module" 2 is outside the tolerance range;

"39" - installation fault: indicates an incorrect connection at the frequency converter input; check the connection of the Mains 1 input source to terminal block XR1;

"41" - load supplied via "static bypass" 3 (normal condition for certain configurations): this display indicates that the load is powered by the Mains 2 via the "static bypass" 3 ;

"51" - charger fault: indicates a fault in the charger module 6 ; contact the after-sales support department;

"61" - rectifier or chopper fault: indicates a fault in the rectifier module 2 ; contact the after-sales support department;

"62" - chopper overtemperature: see fault "22";

"63" - fuses blown on Mains 1 input: indicates that one or more fuses have blown in the rectifier module 2 ; contact the after-sales support department;

"65" - chopper overload: indicates that the active power consumed is too high. Reduce the load;

"71" - internal communication fault: indicates a Comet internal fault; contact the after-sales support department;

"72" - internal communication self-test fault: see fault "71";

"73" - CPU board self-test fault: see fault "71".

manual bypass

if the load is no longer supplied, a manual bypass operation enabling supply is possible, while waiting for the after-sales support personnel;

proceed as follows:

turn off the input power switch 1 ,

switch the battery circuit breaker 4 to "off" position,

check that all lights are off,

turn the "manual bypass" switch 8 as indicated in figure 24 from the "NORMAL" position to the "BYPASS" position.

Merlin Gerin by MGE UPS SYSTEMS

Comet installation and user manual: E-6761200XT/FA

7.3

Page 33
Image 33
MGE UPS Systems Comet TM 5 - 30 kVA user manual Manual bypass, Chopper overtemperature see fault

Comet TM 5 - 30 kVA specifications

MGE UPS Systems Comet TM 5 - 30 kVA is a reliable and efficient uninterruptible power supply (UPS) designed to ensure the smooth operation of critical systems in various applications. This UPS is particularly suited for data centers, telecommunications, and industrial environments that require high availability and robust power protection.

One of the main features of the Comet TM series is its modular design, which allows users to scale the UPS capacity as needed. This flexibility is crucial for businesses that anticipate growth or fluctuating power requirements. The UPS is available in a range of capacities, from 5 kVA to 30 kVA, allowing for tailored solutions that fit specific power needs.

The Comet TM is equipped with advanced double conversion technology, which provides clean and reliable power, isolating the connected equipment from input voltage disturbances. This technology ensures that any fluctuations in the mains supply, such as voltage sags or surges, do not affect the operation of sensitive electronic devices. Additionally, this UPS features a wide input voltage range that contributes to improved efficiency and reduced energy consumption.

An impressive aspect of the Comet TM is its high-efficiency mode, which optimizes energy consumption while maintaining power quality. This mode reduces operating costs and contributes to lower carbon footprints, making it an environmentally friendly choice. Furthermore, the UPS incorporates intelligent battery management systems, which enhance battery performance and extend their lifespan. This is essential in minimizing downtime and ensuring that backup power is readily available when needed.

The user-friendly interface of the Comet TM allows for easy monitoring and management of the system. With graphical displays and comprehensive alarms, users can promptly identify potential issues and take corrective actions. Remote management capabilities are also built into the system, enabling users to monitor and control the UPS remotely, which is particularly beneficial for businesses that operate across multiple locations.

In summary, the MGE UPS Systems Comet TM 5 - 30 kVA is designed for organizations that need reliable power protection and high efficiency. With its modular scalability, advanced double conversion technology, high-efficiency mode, intelligent battery management, and user-friendly interface, the Comet TM series stands out as a robust solution for critical power applications. Its combination of features ensures that businesses can maintain uninterrupted operations while benefiting from cost savings and a reduced environmental impact.