Galaxy PWTM 100 to 225 kVA

list of primary messages

LOAD PROTECTED

ON-LINE MODE

This is the normal display when there are no alarms or problems and the load is cor- rectly supplied by the inverter, in on-line mode.

LOAD PROTECTED

PARALLEL ON-LINE MODE

This is the normal display when there are no alarms or problems and the load is cor- rectly supplied by the inverter in a parallel UPS system, in on-line mode.

LOAD NOT PROTECTED

ON-LINE MODE

This display indicates that the load is not supplied by the inverter, or that there is no battery backup. The arrow indicates the presence of one or more problems specified in secondary messages.

The buzzer sounds continuously.

LOAD NOT PROTECTED

PARALLEL ON-LINE MODE

Situation identical to that in the previous screen, but for parallel UPS systems.

LOAD PROTECTED BATTERY DISCHARGING Remaining battery time (min) = XX % kW used = XXX

The load is supplied by the inverter, but the normal AC source is down or outside tolerances and power is supplied by the battery.

This message indicates the remaining bat- tery time in minutes prior to inverter shut- down and the percent load. The battery time calculation takes into account:

the percentage of full rated load power currently being drawn;

the type of battery;

battery temperature;

battery age.

The buzzer sounds slowly and discontinu- ously.

LOAD PROTECTED, LOW-BATTERY SHUTDOWN WARNING,

Remaining battery time (min) = XX % kW used = XXX

This message replaces the preceding if the power outage persists and the warning level has been reached.

The user is warned that the battery is about to shut down.

The buzzer sounds rapidly and discontinu- ously.

LOAD PROTECTED

ECO MODE

This is the normal display when there are no problems: the load is supplied by the inverter or the bypass AC source, and bat- tery backup is available.

LOAD NOT PROTECTED

ECO MODE

This display indicates that the load is sup- plied but has no battery backup. The arrow indicates the presence of one or more problems specified in secondary messages.

The buzzer sounds continuously.

LOAD FORCED TO INVERTER ECO MODE

The load has been transferred to the inverter following a specific request by the user.

16

Control-panel Display

Page 24
Image 24
MGE UPS Systems Galaxy PW user manual Galaxy Pwtm 100 to 225 kVA List of primary messages, Load Protected ON-LINE Mode

Galaxy PW specifications

The MGE UPS Systems Galaxy PW is a high-performance uninterruptible power supply designed to provide reliable power protection for critical systems in various environments, including data centers, industrial settings, and commercial facilities. Known for its advanced features and innovative technologies, the Galaxy PW is engineered to ensure seamless operation, even in the event of power disturbances.

One of the standout features of the Galaxy PW is its modular design, allowing for easy scalability and flexibility. This design enables users to customize the power capacity according to their specific needs, accommodating future growth without requiring a complete system overhaul. The modular architecture consists of interchangeable power modules that can be easily added or replaced, ensuring minimal downtime and optimized performance.

The Galaxy PW uses cutting-edge double-conversion technology, which provides a high level of power quality and reliability. This technology ensures that any fluctuations in input power do not affect the output, delivering clean and stable electricity to connected equipment. This is particularly essential for sensitive electronics that require a consistent power supply to function correctly.

Another significant characteristic of the Galaxy PW is its energy efficiency. The UPS is designed to operate at high efficiency levels, often exceeding 96%. This not only helps in reducing the overall energy consumption but also lowers operational costs and reduces the carbon footprint of the facility. The Eco-Mode feature allows the UPS to deliver power with minimal energy loss during normal operating conditions.

The Galaxy PW is equipped with advanced communication and management features, including an intuitive graphical LCD display that provides real-time information on the system's status and performance metrics. Users can monitor input and output voltages, current load levels, and battery health at a glance. Additionally, the UPS supports various communication protocols and interfaces, facilitating integration with building management systems and remote monitoring tools.

Safety and reliability are also top priorities for the Galaxy PW. The system features robust battery management to extend the lifespan of the batteries while ensuring optimal performance. The UPS is designed with several protections, including overload, short-circuit, and thermal protection, to safeguard both the UPS and connected loads.

In summary, the MGE UPS Systems Galaxy PW integrates modularity, energy efficiency, advanced monitoring, and robust protection features to deliver unmatched reliability for critical power applications. Its innovative design and technologies make it an ideal choice for businesses seeking a reliable power protection solution.