battery maintenance

Consult the instructions supplied by the battery manufacturer. Below are a few general indications:

sealed lead-acid batteries: these bat- teries require no maintenance, but check the terminals of each cell from time to time and clean if necessary;

vented lead-acid batteries:

check the electrolyte level regularly and add water if necessary,

check the voltage of each cell to deter- mine if it is necessary to equalize the bat- tery,

check the terminals of each cell and clean if necessary.

CAUTION

Battery maintenance is undertaken with the system powered up. Operations must be carried out in accordance with applicable safety regula- tions by qualified personnel using insulated tools, gloves and safety goggles.

Batteries contain danger- ous substances that will harm the environment if thrown away. If you change the bat- teries yourself, call on quali- fied organizations for battery recovery and recycling.

visual check

Power down the system prior to any maintenance operations.

Note: in redundant parallel UPS systems the check may be carried out successively on each UPS unit without interrupting the load. In other configurations, the load must be supplied via the maintenance bypass (see "maintenance bypass" in the "Alarm" section);

clean the system regularly, particularly the air filter inlet and outlet grills. Check that the air circulates freely in the cabi- nets. Use a vacuum cleaner if necessary;

check that nothing hinders the ventila- tion at the top and at the back of the sys- tem.

functional check

Check that lights 1 , 2 and 3 on the control panel are not red, to avoid an interruption in the supply of power to the load due to incorrect transfer conditions or a battery problem;

press the "inverter OFF" button and check that the buzzer and control panel lights function correctly (see the section on operating modes in the introduction);

press the "inverter ON" button and check again that the control panel lights function correctly;

run a transfer to battery test. With the inverter on, open input circuit breaker Q1. The orange "battery" light on the control panel should light. After two minutes on battery power, close input circuit breaker Q1. The rectifier/charger should automati- cally restart and the orange "battery" light on the control panel should go off;

in parallel systems, run these tests on each UPS unit.

PbPb

30

Maintenance

Page 38
Image 38
MGE UPS Systems Galaxy PW user manual Battery maintenance, Visual check, Functional check

Galaxy PW specifications

The MGE UPS Systems Galaxy PW is a high-performance uninterruptible power supply designed to provide reliable power protection for critical systems in various environments, including data centers, industrial settings, and commercial facilities. Known for its advanced features and innovative technologies, the Galaxy PW is engineered to ensure seamless operation, even in the event of power disturbances.

One of the standout features of the Galaxy PW is its modular design, allowing for easy scalability and flexibility. This design enables users to customize the power capacity according to their specific needs, accommodating future growth without requiring a complete system overhaul. The modular architecture consists of interchangeable power modules that can be easily added or replaced, ensuring minimal downtime and optimized performance.

The Galaxy PW uses cutting-edge double-conversion technology, which provides a high level of power quality and reliability. This technology ensures that any fluctuations in input power do not affect the output, delivering clean and stable electricity to connected equipment. This is particularly essential for sensitive electronics that require a consistent power supply to function correctly.

Another significant characteristic of the Galaxy PW is its energy efficiency. The UPS is designed to operate at high efficiency levels, often exceeding 96%. This not only helps in reducing the overall energy consumption but also lowers operational costs and reduces the carbon footprint of the facility. The Eco-Mode feature allows the UPS to deliver power with minimal energy loss during normal operating conditions.

The Galaxy PW is equipped with advanced communication and management features, including an intuitive graphical LCD display that provides real-time information on the system's status and performance metrics. Users can monitor input and output voltages, current load levels, and battery health at a glance. Additionally, the UPS supports various communication protocols and interfaces, facilitating integration with building management systems and remote monitoring tools.

Safety and reliability are also top priorities for the Galaxy PW. The system features robust battery management to extend the lifespan of the batteries while ensuring optimal performance. The UPS is designed with several protections, including overload, short-circuit, and thermal protection, to safeguard both the UPS and connected loads.

In summary, the MGE UPS Systems Galaxy PW integrates modularity, energy efficiency, advanced monitoring, and robust protection features to deliver unmatched reliability for critical power applications. Its innovative design and technologies make it an ideal choice for businesses seeking a reliable power protection solution.