Users Manual & Installation Guide

PV- 5127: Power supply module with UPS

RS232 Status signals

The Battery low and Mains failure signals together can tell three different states:

Mains failure

Battery low

Status

0

0

Running normally on mains power.

1

0

Mains alarm, running on battery. The CPU is advised to shut down if

 

 

mains power doesn’t come back within reasonable time. This time

 

 

should be configured in the UPS monitoring software.

1

1

Critical alarm. The CPU is advised to shut down immediately.

 

 

This happens in two situations:

 

 

During mains failure and the battery is critically low.

 

 

When the system is too hot.

RS232 Shutdown signal

When the CPU activates the Shutdown signal for one second, the PV-5127 immediately turns off the +5V and +12V power, and, if mains is not present, also the +5V STB. Pulses shorter than one second have no effect. For details, please see the section ATX and Softoff state machines.