Miele CS 1028 installation instructions Installation, Safety distance from the wall covering

Models: CS 1028

1 44
Download 44 pages 20.21 Kb
Page 25
Image 25
Installation

Installation

Safety distance from the wall covering

If a wall covering is installed, a minimum safety distance must be maintained between the countertop cut-out and the covering, since high temperatures can damage these materials.

If the covering is made of a combustible material (such as wood), the distance between the countertop cut-out and the wall covering must be a minimum of 2" (50 mm).

For coverings made of non-combustible materials (such as metal, marble, granite or ceramic tiles) the minimum safety distance ￿ between the countertop cut-out and the wall covering must be 2" (50 mm) minus the thickness of the covering. For example: thickness of wall covering 9/16" (15 mm)

2" (50 mm) - 9/16" (15 mm) = minimum safety distance 1 3/8" (35 mm).

￿Wall frame

￿Wall covering

x = thickness of the wall covering

￿Countertop

￿Countertop cut-out

￿Minimum safety distance

with flammable materials 2" (50 mm)

with non-flammable materials 2" (50 mm) minus x

25

Page 25
Image 25
Miele CS 1028 installation instructions Installation, Safety distance from the wall covering