4-7. Connecting Work Clamp
1
2
1Work Clamp
2Workpiece
Connect work clamp to a clean,
802
4-8. Connecting Input Power
1
2 |
Check input voltage available at site. 1 Changeover Switch
Switch is accessible through slot in rear panel.
2 Changeover Switch Label
Look at label to find correct switch position.
YBe sure input power connection meets all applicable national, regional, and local electrical codes.
3Grounded 120 VAC Receptacle
Y To use rated output (see spec- |
ifications), connect the unit to |
an individual branch circuit |
capable of carrying the effec- |
tive (eff) current for the output |
being used. The unit must |
have a properly sized plug |
3
4
installed and the circuit must |
be protected by properly |
sized fuses or circuit break- |
ers. |
A 120 volt, 20 ampere (minimum) individual branch circuit protected by
4Plug From Unit Connect plug to receptacle.
If an extension cord is necessary, select a cord of 12 AWG for up to 53 ft (16 m).
To connect unit to 230 VAC input power, a customer supplied plug is necessary (see Section
A 230 volt, 15 ampere (minimum) individual branch circuit protected by
If an extension cord is necessary, select a cord of 14 AWG for up to 133 ft (41 m).
YSpecial installation may be required where gasoline or volatile liquids are present − see NEC Article 511 or CEC Section 20.