Miller Electric Regency 250 Remote 14 Receptacle Information, Electrical Service Guide, Socket

Models: Regency 250

1 28
Download 28 pages 11 Kb
Page 16
Image 16

2-7. Remote 14 Receptacle Information

A

J

B

K

I

 

 

C

L N

H

D

M

G

 

E

F

Ref. 121 470-E / Ref. 192 412

Socket*

Socket Information

A

24 volts ac. Protected by circuit breaker CB2.

24 VOLTS AC

 

B

Contact closure to A completes 24 volts ac con-

 

tactor control circuit.

I

115 volts ac. Protected by circuit breaker CB1.

115 VOLTS AC

 

J

Contact closure to I completes 115 volts ac con-

 

tactor control circuit.

G

Circuit common for 24 and 115 volts ac circuits.

GND

 

K

Chassis common.

*The remaining sockets are not used.

2-8. Electrical Service Guide

Input Voltage

200

230

460

 

 

 

 

Input Amperes At Rated Output

46

40

20

 

 

 

 

Max Recommended Standard Fuse Rating In Amperes 1

 

 

 

Time-Delay 2

50

50

25

Normal Operating 3

70

60

30

 

 

 

 

Min Input Conductor Size In AWG/Kcmil

8

8

12

 

 

 

 

Max Recommended Input Conductor Length In Feet (Meters)

89

118

188

(27)

(36)

(57)

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil

8

10

12

 

 

 

 

Reference: 1999 National Electrical Code (NEC)

1Consult factory for circuit breaker applications.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).

OM-293 Page 12

Page 16
Image 16
Miller Electric Regency 250 manual Remote 14 Receptacle Information, Electrical Service Guide, Socket, Input Voltage