2-7. Remote 14 Receptacle Information
A | J | |
B | K | I |
|
| |
C | L N | H |
D | M | G |
| E | F |
Ref. 121
Socket* | Socket Information |
A | 24 volts ac. Protected by circuit breaker CB2. |
24 VOLTS AC |
|
B | Contact closure to A completes 24 volts ac con- |
| tactor control circuit. |
I | 115 volts ac. Protected by circuit breaker CB1. |
115 VOLTS AC |
|
J | Contact closure to I completes 115 volts ac con- |
| tactor control circuit. |
G | Circuit common for 24 and 115 volts ac circuits. |
GND |
|
K | Chassis common. |
*The remaining sockets are not used.
2-8. Electrical Service Guide
Input Voltage | 200 | 230 | 460 | |
|
|
|
| |
Input Amperes At Rated Output | 46 | 40 | 20 | |
|
|
|
| |
Max Recommended Standard Fuse Rating In Amperes 1 |
|
|
| |
50 | 50 | 25 | ||
Normal Operating 3 | 70 | 60 | 30 | |
|
|
|
| |
Min Input Conductor Size In AWG/Kcmil | 8 | 8 | 12 | |
|
|
|
| |
Max Recommended Input Conductor Length In Feet (Meters) | 89 | 118 | 188 | |
(27) | (36) | (57) | ||
| ||||
|
|
|
| |
Min Grounding Conductor Size In AWG/Kcmil | 8 | 10 | 12 | |
|
|
|
|
Reference: 1999 National Electrical Code (NEC)
1Consult factory for circuit breaker applications.
2
3“Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).