MODEL NUMBER

MBK550E

 

MBK750E

 

 

 

 

 

 

 

 

Acceptable Input voltage

0 - 150VAC

 

 

 

Input voltage (AC Mode)

120VAC setting (default):85-132VAC, Selectable: 75/80-132VAC

 

 

 

127VAC setting: 85-140VAC, Selectable: 75/80-140VAC

 

 

Output voltage (AC Mode)

120VAC setting: 105-132VAC, 127VAC setting: 105-140V

 

 

Nominal input frequency

50 or 60 Hz, autosensing

 

 

Input protection

Resettable circuit breaker

 

 

Frequency limits (AC Mode)

50 or 60 Hz, +/-6Hz

 

 

Transfer time

2-6 mS typical

 

 

 

Maximum load

550VA/330W

 

750VA/450W

 

 

On-battery output voltage

Default 120VAC (User

selectable at 120/127VAC)

 

 

On-battery frequency

50/60 Hz, +/-.5 Hz, unless synchronized to utility

 

 

On-battery waveshape

Simulated Sine Wave

 

 

Protection

Over current, short circuit protected and latching shutdown

 

 

Surge energy rating (one time,

500 J

 

 

 

10/1000 uS waveform)

 

 

 

 

 

Surge current capability

6500 Amps total

 

 

 

(one time, 8/20 uS waveform)

 

 

 

Surge response time

0 ns (instantaneous) normal mode; <5 ns common mode

 

 

Surge voltage let-through (as

<5%

 

 

 

a percentage of an applied

 

 

 

ANSI C62.41 Cat. A +/-6 kV)

 

 

 

 

 

Noise filter

Normal and common mode EMI/RFI suppression

 

 

Battery type: Sealed, non-

1-12V7Ah

 

2-12V7Ah

 

 

spillable, maintenance free,

 

 

 

lead-acid

 

 

 

 

 

Typical battery life

2-4 years, depending on discharge cycles and ambient temp

 

 

Typical recharge time

8 hours from total discharge

 

 

10 Base-T surge protection let-

 

 

 

 

 

through (as a percentage of

<5%

 

 

 

an applied +/-6 kV 1.2/50 us,

 

 

 

500 a 8/20 uS test)

 

 

 

 

 

Telephone line surge protec-

 

 

 

 

 

tion let-through (as a percent-

<1%

 

 

 

age of an applied +/-6 kV 1.2/

 

 

 

 

 

 

 

 

50 us, 500a 8/20 uS test)

 

 

 

 

 

Runtime: Half Load

11-Minutes

 

19-Minutes

 

 

Runtime: Full Load

3-Minutes

 

5-Minutes

 

 

Electromagnetic immunity

IEC 801-2 level IV, 801-4 level IV, 801 -5 level III

 

 

Audible noise at 1 m (3 ft.)

<45 dBA

 

 

 

Size - Net

7.56 x 12.56 x 6.38"

 

 

H X D X W

192 x 319 x 162 mm

 

 

Size - Shipping

13 x 18.9 x 11.4"

 

 

 

H X D X W

330 x 480 x 290 mm

 

 

Weight - Net (Shipping)

18.74 (22)lb

 

25.8 (29)lb

 

 

8.5 (9.7)Kg

 

11.7 (12.9)Kg

 

 

 

 

 

 

Safety and approvals

UL1778, cUL

(CSA 22.1)

 

 

EMC Verification

FCC Class B, CE certified