English
TURNING THE UNIT ON/OFF
ON / OFF / Test Button
Press and release the ON/OFF/Test Button after one beep to turn the UPS ON and supply power to the load. The load is immediately powered while the UPS runs a
SELF TEST
The self test feature is useful to verify the correct operation of the UPS and the condition of the batteries. With the UPS in the normal
Note: The UPS will automatically perform a self test on
DIP SWITCH SETTINGS
The DIP Switch setting may be changed by the user to set the desired Inverter (on battery) output voltage and the Low voltage transfer set points. The DIP Switches must be set to the desired Inverter output voltage and the Low voltage transfer set points then, the UPS must be turned OFF and restarted to reconfigure the microprocessor and save the changes. The Inverter (on battery) output voltage setting can be either 120VAC (default) or 127VAC. Changing the In- verter output voltage to 127VAC, will also change the Overvoltage set point from 132VAC (default) to 140VAC. The Low voltage transfer set points can be changed to 85VAC (default) or 80VAC or 75VAC.
Inverter output voltage | Low voltage transfer |
| ||
Switch | 2 | 3 | ||
Switch | 1 | 75V |
|
|
120V |
| 80V |
|
|
127V |
| 85V |
|
|
9