2033C SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-2

WARNING 2

This UPS does not include an AC input circuit breaker (MCCB) to protect the bypass and main input circuit. The AC input circuit breaker (MCCB) is to be field supplied and installed. Circuit breaker (MCCB) specifications are as follows:

Capacity

AC input

AC input

Recommended

(kVA)

Voltage (Vac)

Rating (Aac)

Breaker (A)

7.5

208

23

30

 

 

 

 

10

208

30

35

 

 

 

 

15

208

45

60

 

 

 

 

20

208

61

75

 

 

 

 

30

208

91

125

 

 

 

 

40

208

121

150

 

 

 

 

50

208

151

200

 

 

 

 

AC output and DC input overcurrent protection and disconnection devices shall be field supplied and installed.