MITSUBISHI | 2033C SERIES UPS | Page Number: |
ELECTRIC | OWNERS / TECHNICAL MANUAL |
WARNING 2
This UPS does not include an AC input circuit breaker (MCCB) to protect the bypass and main input circuit. The AC input circuit breaker (MCCB) is to be field supplied and installed. Circuit breaker (MCCB) specifications are as follows:
Capacity | AC input | AC input | Recommended |
(kVA) | Voltage (Vac) | Rating (Aac) | Breaker (A) |
7.5 | 208 | 23 | 30 |
|
|
|
|
10 | 208 | 30 | 35 |
|
|
|
|
15 | 208 | 45 | 60 |
|
|
|
|
20 | 208 | 61 | 75 |
|
|
|
|
30 | 208 | 91 | 125 |
|
|
|
|
40 | 208 | 121 | 150 |
|
|
|
|
50 | 208 | 151 | 200 |
|
|
|
|
AC output and DC input overcurrent protection and disconnection devices shall be field supplied and installed.
MITSUBISHI ELECTRIC 2033C SERIES UPS