Mitsubishi Electronics 2033C AC Input Characteristics, Battery, AC Output, Environmental

Models: 2033C

1 48
Download 48 pages 57.32 Kb
Page 21
Image 21

MITSUBISHI

 

 

2033C SERIES UPS

 

 

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

 

1-15

 

 

TABLE 1.3 Detail of Specifications

 

 

 

 

 

 

 

 

Rated Output kVA

7.5

 

 

10

15

20

30

 

40

 

50

Rated Output kW

6

 

 

8

12

16

24

 

32

 

40

 

AC INPUT CHARACTERISTICS

 

 

 

 

 

Configuration

3 phase, 4 wire

 

 

 

 

 

 

 

Voltage

120/208 V

+15% ~ -25%

 

 

 

 

 

 

Frequency

60 Hz +/- 5%

 

 

 

 

 

 

 

Reflected Current THD

4% typ. at 100% load; 7% typ. at 50% load

 

 

 

 

 

 

 

 

BATTERY

 

 

 

 

 

 

Type

VRLA

 

 

 

 

 

 

 

 

Ride Through

8min.

 

5min.

11min.

7min.

5min.

 

 

 

 

(at 100% load)

 

 

 

 

 

 

 

 

 

 

 

Nominal Voltage

360 Vdc

 

 

 

 

 

 

 

 

Minimum Voltage

300 Vdc

 

 

 

 

 

 

 

 

Number of Cells

180

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC OUTPUT

 

 

 

 

 

 

Configuration

3 phase, 3 or 4 wire

 

 

 

 

 

 

 

Voltage

120/208 V

 

 

 

 

 

 

 

 

Voltage Stability

+/-1%

 

 

 

 

 

 

 

 

 

 

Frequency

60 Hz

 

 

 

 

 

 

 

 

Frequency Stability

+/-0.01% in free running mode

 

 

 

 

 

 

Power Factor

0.8 nominal

 

 

 

 

 

 

 

Power Factor range

0.8 ~ 1.0 lagging (within output kW rating)

 

 

 

 

 

Voltage THD

2% typical THD at 100% Linear Load

 

 

 

 

 

 

4% typical THD at 100% non-linear load

 

 

 

 

 

Transient Response

+/-3% typical at 100% load step

 

 

 

 

 

 

 

+/-1% typical at loss/return of AC power

 

 

 

 

 

 

+/-3% typical at load transfer to/from static bypass

 

 

 

 

Transient Recovery

16.7 ms

 

 

 

 

 

 

 

 

Voltage Unbalance

2% typical at 100% unbalanced load

 

 

 

 

 

Phase Displacement

1deg. typical at 100% load

 

 

 

 

 

 

Inverter Overload

150% for 1 minute

 

 

 

 

 

 

 

System Overload

150% for 1 minute, 1000% for 1 cycle (with bypass available)

 

Bypass Overload

150% for 1 minute, 1000% for 1 cycle

 

 

 

 

 

Crest Factor Capabilities

3:1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENVIRONMENTAL

 

 

 

 

 

 

Cooling

Forced Air

 

 

 

 

 

 

 

Operating Temperature

32F ~ 104F (0C ~ 40C).

 

 

 

 

 

 

 

Recommended 59F ~ 77F (15C ~ 25C)

 

 

 

 

Relative Humidity

5% ~ 95% Non Condensing

 

 

 

 

 

 

Altitude

0 ~ 5000 feet No De-rating

 

 

 

 

 

 

Location

Temperature-controlled, indoor area free of conductive contaminants

 

MITSUBISHI ELECTRIC 2033C SERIES UPS

Page 21
Image 21
Mitsubishi Electronics 2033C technical manual AC Input Characteristics, Battery, AC Output, Environmental