MITSUBISHI |
| 20033C SERIES UPS |
|
| Page Number: | |||
ELECTRIC | OWNERS / TECHNICAL MANUAL |
|
| |||||
| Failure Code List |
|
|
|
|
|
|
|
|
|
|
|
| Note 1 | Note 2 | Note 3 |
|
| LCD Failure Code | Status |
| Guidance | Buzzer | External send- | Failure LED |
|
|
|
|
|
|
| out contact |
|
|
| 00 | Test mode (Pulse check) |
| - | [1] | - | - |
|
|
|
|
|
|
|
|
|
|
| 01 | Maintenance mode |
| - | [1] | - | - |
|
|
|
|
|
|
|
|
|
|
| 10 | Battery circuit abnormal |
| Call service engineer | [1] | Minor | Flicker |
|
|
|
|
|
|
|
|
|
|
| 11 | Battery test |
| - | - | - | - |
|
|
|
|
|
|
|
|
|
|
| 12 | Battery circuit abnormal |
| Call service engineer | [1] | Minor | Flicker |
|
|
|
|
|
|
|
|
|
|
| 13 | Battery depleted warning |
| - | [1] | Alarm | Flicker |
|
|
|
|
|
|
|
|
|
|
| 14 | Battery depleted |
| - | [2] | Alarm | Lit up |
|
|
|
|
|
|
|
|
|
|
| 15 | Battery temperature abnormal |
| Check battery | [1] | Alarm | Flicker |
|
|
|
|
|
|
|
|
|
|
| 16 | Battery temperature abnormal |
| Check battery | [1] | Minor | Flicker |
|
|
|
|
|
|
|
|
|
|
| 17 | Battery charge voltage abnormal |
| Call service engineer | [1] | Alarm | Flicker |
|
|
|
|
|
|
|
|
|
|
| 18 | DC voltage abnormal |
| Call service engineer | [1] | Minor | Flicker |
|
|
|
|
|
|
|
|
|
|
| 19 | Battery depleted (Converter |
| Check AC input voltage | [2] | Major | Lit up |
|
| overload) |
|
| |||||
|
|
|
|
|
|
|
| |
| 21 | AC input voltage out of range |
| Check AC input voltage | [1] | Alarm | - |
|
|
|
|
|
|
|
|
|
|
| 22 | AC input phase rotation error |
| Check AC input voltage | [1] | Minor | Flicker |
|
|
|
|
|
|
|
|
|
|
| 23 | Converter overload |
| Call service engineer | [1] | Alarm | Flicker |
|
|
|
|
|
|
|
|
|
|
| 24 | Converter over current |
| Call service engineer | [1] | Minor | Flicker |
|
|
|
|
|
|
|
|
|
|
| 25 | Converter abnormal (DCOV) |
| Call service engineer | [2] | Major | Lit up |
|
|
|
|
|
|
|
|
|
|
| 26 | Converter abnormal (DCUV) |
| Call service engineer | [2] | Major | Lit up |
|
|
|
|
|
|
|
|
|
|
| 27 | Converter abnormal |
| Call service engineer | [2] | Major | Lit up |
|
|
|
|
|
|
|
|
|
|
| 28 | Converter abnormal at |
| Call service engineer | [2] | Major | Lit up |
|
|
|
|
|
|
|
|
|
|
| 31 | Inverter voltage abnormal |
| Call service engineer | [1] | Minor | Flicker |
|
|
|
|
|
|
|
|
|
|
| 32 | Inverter abnormal (VLOV) |
| Call service engineer | [2] | Major | Lit up |
|
|
|
|
|
|
|
|
|
|
| 33 | Inverter abnormal (VLUV) |
| Call service engineer | [2] | Major | Lit up |
|
|
|
|
|
|
|
|
|
|
| 34 | Inverter abnormal (OC) |
| Call service engineer | [2] | Major | Lit up |
|
|
|
|
|
|
|
|
|
|
| 35 | Inverter abnormal |
| Call service engineer | [2] | Major | Lit up |
|
|
|
|
|
|
|
|
|
|
| 36 | 52C abnormal |
| Call service engineer | [1] | Minor | Flicker |
|
|
|
|
|
|
|
|
|
|
| 37 | 52C abnormal |
| Call service engineer | [1] | Minor | Flicker |
|
|
|
|
|
|
|
|
|
|
| 41 | Bypass voltage out of range |
| Check bypass input | - | Alarm | Flicker |
|
MITSUBISHI ELECTRIC 2033C SERIES UPS