Mitsubishi Electronics GB-50ADA-A Performing the Operations, Block name, On/Off, Operation mode

Models: GB-50ADA-A GB-50ADA-J AG-150A

1 16
Download 16 pages 3.12 Kb
Page 13
Image 13
3-3 Performing the Operations

3-3 Performing the Operations

Text below explains how to perform air conditioner or general equipment or hot water supply operations.

3-3-1 Performing the operations that target one group

When you click on a group icon in the operation condition monitoring screen, the operation screen for that group will appear. The items shown in this screen are the current operation conditions. Modify the items you want to change and click [OK] to confirm the operation details. Click [Cancel] to return to the previous screen without making any changes.

Block name

The name of the block is displayed here.

ON/OFF

Click to switch to ON or OFF.

Operation prohibition mark

If the prohibit setting has been set for an operation, the prohibition mark will be displayed.

Operation mode

Click to switch the operation mode.

Set temperature

Click to adjust the set temperature.

Air direction

Click to adjust the air direction.

Filter sign

Click to reset the filter sign.

Group name

The name of the group is displayed here.

Central control mark

This is displayed when the units are centrally controlled.

Interlocked ventilator

ON/OFF

Click to switch interlocked ventilator ON or OFF.

Fan speed of interlocked ventilator

Click to adjust the fan speed of the interlocked ventilator.

Fan speed

Click to adjust the fan speed.

OK button

Click to confirm the operation details. You must press the OK button for the operation to take effect.

Cancel button

Click to cancel all operations.

Item

ON/OFF *1

Operation mode

Set temperature

Air direction

Fan speed

Filter sign

Description

Click [ON] or [OFF] to switch to ON or OFF.

Note: Ventilation units that are interlocked with a given group of indoor units will turn on and off when this switch is turned on and off. To switch on/off the interlocked ventilation units only, use the “Ventilation ON/OFF” button.

Click [Cool], [Dry], [Fan], [Heat] or [Auto] to switch the operation mode.

Note: This item will not appear if the operation mode switching function is not available.

Note: Some unit models do not support certain operation modes. Unsupported operation modes are not displayed.

Note: For K control models, all modes are displayed, however, choose only the modes that can be operated.

Note: If it is a ventilator group, select [Bypass], [Heat Recovery] or [Auto].

Note: When making the settings for the hot water supply group, elect from [Heating], [Heating ECO], [Hot Water], [Anti-freeze], and [Cooling].

Click 3-3-1 Performing the operations that target one groupBlock name to adjust the set temperature.

For [Cool] and [Dry], the setting range is 19 ~ 30°C/67 ~ 87°F, for [Heat] it is 17 ~ 28°C/63 ~ 83°F, and for [Auto] it is 19 ~ 28°C/67 ~ 83°F.

Note: This item will not appear if the temperature setting function is not available.

Note: The temperature setting range varies depending on the unit model.

Note: If the setting range for set temperature is restricted, the temperature setting range will be smaller.

Note: The temperature setting range for the hot water supply group is as follows:

[Heating] mode

: 30°C

~ 45°C or 50°C / 87°F ~ 113°F or 122°F

[Heating ECO] mode : 30°C

~ 45°C / 87°F ~ 113°F

[Hot Water] mode

: 30°C

~ 90°C or 70°C / 87°F ~ 194°F or 158°F

[Anti-freeze] mode

: 10°C

~ 45°C / 50°F ~ 113°F

[Cooling] mode

: 10°C

~ 30°C / 50°F ~ 87°F.

Click ON/OFFOperation prohibition mark to adjust the air direction.

Note: If it is a model that does not support air direction adjustment, this item is not displayed.

Note: Available functions vary depending on the unit model.

Click Operation modeSet temperature to adjust the fan speed.

Note: If it is a model that does not support fan speed adjustment, this item is not displayed.

Note: Available functions vary depending on the unit model.

Click [Reset] to specify whether to reset the filter sign. It is set to reset when a green indicator is displayed on the left of Reset ([Air directionReset]).

Note: If filter signs are not triggered in the group, then this item is not displayed.

12

Page 13
Image 13
Mitsubishi Electronics GB-50ADA-A Performing the Operations, Performing the operations that target one group, Block name