3-3 Performing the Operations
Text below explains how to perform air conditioner or general equipment or hot water supply operations.
3-3-1 Performing the operations that target one group
When you click on a group icon in the operation condition monitoring screen, the operation screen for that group will appear. The items shown in this screen are the current operation conditions. Modify the items you want to change and click [OK] to confirm the operation details. Click [Cancel] to return to the previous screen without making any changes.
Block name
The name of the block is displayed here.
ON/OFF
Click to switch to ON or OFF.
Operation prohibition mark
If the prohibit setting has been set for an operation, the prohibition mark will be displayed.
Operation mode
Click to switch the operation mode.
Set temperature
Click to adjust the set temperature.
Air direction
Click to adjust the air direction.
Filter sign
Click to reset the filter sign.
Group name
The name of the group is displayed here.
Central control mark
This is displayed when the units are centrally controlled.
Interlocked ventilator
ON/OFF
Click to switch interlocked ventilator ON or OFF.
Fan speed of interlocked ventilator
Click to adjust the fan speed of the interlocked ventilator.
Fan speed
Click to adjust the fan speed.
OK button
Click to confirm the operation details. You must press the OK button for the operation to take effect.
Cancel button
Click to cancel all operations.
Item
ON/OFF *1
Operation mode
Set temperature
Air direction
Fan speed
Filter sign
Description
Click [ON] or [OFF] to switch to ON or OFF.
Note: Ventilation units that are interlocked with a given group of indoor units will turn on and off when this switch is turned on and off. To switch on/off the interlocked ventilation units only, use the “Ventilation ON/OFF” button.
Click [Cool], [Dry], [Fan], [Heat] or [Auto] to switch the operation mode.
Note: This item will not appear if the operation mode switching function is not available.
Note: Some unit models do not support certain operation modes. Unsupported operation modes are not displayed.
Note: For K control models, all modes are displayed, however, choose only the modes that can be operated.
Note: If it is a ventilator group, select [Bypass], [Heat Recovery] or [Auto].
Note: When making the settings for the hot water supply group, elect from [Heating], [Heating ECO], [Hot Water],
Click to adjust the set temperature.
For [Cool] and [Dry], the setting range is 19 ~ 30°C/67 ~ 87°F, for [Heat] it is 17 ~ 28°C/63 ~ 83°F, and for [Auto] it is 19 ~ 28°C/67 ~ 83°F.
Note: This item will not appear if the temperature setting function is not available.
Note: The temperature setting range varies depending on the unit model.
Note: If the setting range for set temperature is restricted, the temperature setting range will be smaller.
Note: The temperature setting range for the hot water supply group is as follows:
[Heating] mode | : 30°C | ~ 45°C or 50°C / 87°F ~ 113°F or 122°F |
[Heating ECO] mode : 30°C | ~ 45°C / 87°F ~ 113°F | |
[Hot Water] mode | : 30°C | ~ 90°C or 70°C / 87°F ~ 194°F or 158°F |
: 10°C | ~ 45°C / 50°F ~ 113°F | |
[Cooling] mode | : 10°C | ~ 30°C / 50°F ~ 87°F. |
Click to adjust the air direction.
Note: If it is a model that does not support air direction adjustment, this item is not displayed.
Note: Available functions vary depending on the unit model.
Click to adjust the fan speed.
Note: If it is a model that does not support fan speed adjustment, this item is not displayed.
Note: Available functions vary depending on the unit model.
Click [Reset] to specify whether to reset the filter sign. It is set to reset when a green indicator is displayed on the left of Reset ([Reset]).
Note: If filter signs are not triggered in the group, then this item is not displayed.
12