Mitsubishi Electronics manual Mapping CLX Data to ICC Database Locations, ICC ETH-1000

Models: ETH-1000

1 36
Download 36 pages 5.96 Kb
Page 26
Image 26
ICC ETH-1000

2.Select the EtherNet/IP tab of the ICC Configuration screen and define the ICC Database locations where data items will be exchanged between the ControlLogix PLC and the ICC module through the Implicit Messaging protocol.

In this example, the “Produce Data Start Address” of the ICC module is set at Database Location 0 and the “Consume Data Start Address” at 2048. These addresses are referring to the database in the ICC module that will be used to transfer data between ICC and the ControlLogix tags. The “Produced” and “Consumed” terms are from the ICC Module perspective. The following diagram is helpful to explain how the data items are assigned and transferred.

ICC ETH-1000

CSC_ICC_ETH100_INT:I

CSC_ICC_ETH100_INT:O

CLX

248 WORDS (Int)

248 WORDS (Int)

DB Locations:

0 - 495

DB Locations:

2048 - 2543

Figure 3 Mapping CLX Data to ICC Database Locations

5-2

Page 26
Image 26
Mitsubishi Electronics Mapping CLX Data to ICC Database Locations, ICC ETH-1000, CSCICCETH100INTI CSCICCETH100INTO