FX2N-32DP-IF Profibus-DP Interface Unit Advanced Devices 4
4-4

4.2.1 32DP-IF Status (M8000 ~ M8009 and D8000 ~ D8009)

Figure 4.2:Momentary Power failuresFigure 4.3:32DP-IF VersionTable 4.3:Special Auxiliary Relays (M8000 ~ M8009)
Diagnostic
Device Name Description
M8000 ()RUN LED monitor ON wh en 32DP-IF is exchanging data with extension I/O
blocks/units and special. This device operate same as RUN
LED.
M8001 ~ M8003 Reserved
M8004 ()
(ref. D8004) Error occurrence ON when one or more error flags (M8060 to M8068) is ON. If
this bit is ON, error number is written in D8004.
M8005, M8006 Reserved
M8007 () ( )
(ref. D8007) Momentary
power failure See Figure 4.2.
M8008, M8009 Reserved
Table 4.4:Special Data Registers (D8000 ~ D8009)
Diagnostic
Device Name Description
D8000 Reserved
D8001 ()32DP-IF version This value is 32DP-IF version code. See Figure 4.3.
D8002, D8003 Reserved
D8004 () ( )Er ro r number
MThe contents of this register identifies which error flag
is active, i.e. if = 8061, identifies M8061
D8005, D8006 Reserved
D8007 () ( )Numb er of
momentary
power failures
This value is counted when M8007 is ON. This value is reset
on full power OFF.
D8008 ()Power failure
detection period Power failure detection period is 10 m s.
D8009 Reserved

AC Power

Exchanged

with DP-master

M8007

Momentary power failure

10 ms

5 ms This time is power failure detection period.

Version No.: Ex. 100 = V1.00

Module Type No.: Ex. 20 = 32DP-IF

dec