Appendix B
B-1
Appendix B:Example Setting User Parameters
For user parameters, refer to chapter 6.

B-1 Example Configuration User Parameters

B-1-1 Example Setting for FX2N-4AD
For BFM’s definition, ref er to FX2N-4AD User’s Manual.

Table B-1:User Parameter FX

2N
-4AD
Using GSD File User
Parameter
Type Description
Using Programming Tool
Byte No. Setting
Value
(Hex)
Register
No.
Setting
Valu e
(Hex)
Higher/
Lower
Byte
0 00 H User
parameter
for 32DP-IF See section 6.1. D200 0000 H Lower
1 00 H Higher
2DA H
User parameter
for spe cial
function
block
(FX2N-4AD)
BFM #30 lower byte: “DA H” D201 07DA H Lower
3 07 H BFM #30 higher byte: “07 H” Higher
4 09 H Total length of parameter bytes for this
special function block is 9 bytes (byte
No. 4 ~ 12). D202 0409 H
Lower
5 04 H Example: number of BFM for data
exchanged every cycle is 4
BFMs (BFM #9 ~ #12). Higher
6 09 H Specified exchange, ex. BFM #9 D203 0A09 H Lower
7 0A H Specified exchange, ex. BFM #10 Higher
8 0B H Specified exchange, ex. BFM #11 D204 0C0B H Lower
9 0C H Specified exchange, ex. BFM #12 Higher
10 80 H
Example: If BFM #0 is set to “1100 H”.
Ch 1: Voltage input mode
Ch 2: Voltage input mode
Ch 3: Current input mode
(4~20 mA)
Ch 4: Current input mode
(4~20 mA)
D205 008 0 H Lower
11 00 H BFM #0 lower byte = “00 H” (ch 1, ch 2) Higher
12 00 H BFM #0 higher byte = “11 H” (ch 3, ch 4) D206 0011 H Lower
-- - Higher
FX2N-32DP-IF Profibus-DP Interface Units