FX2N-32DP-IF Profibus-DP Interface Unit Advanced Devices 4
4-5

4.2.2 Profibus-DP Network Status (M8020 ~ M8039 and D8020 ~ D8039)

Note 1: Swap byte order
Some DP-masters handle lower bytes and higher bytes of a word in a reverse order than the 32DP-
IF. To enable the module to communicate with these masters, bit 0 of data register D8021 can be set.
If bit 0 is “1”, the low order byte and the high order byte of each user data word and of the user spe-
cific diagnosis will be swapped. Bit 0 of D8021 can also be set or reset by the second user defined
parameter byte received from a master. The default value after power up is “0”.

Table 4.5:Special Auxiliary Relays (M8020 ~ M8039)

Diagnostic
Device Name Description
M8020 Setting parameter
When this bit is changed from OFF to ON, the parameter D200
~ D299 (made by the programming tool) is written to special
function blocks’ BFM. After the write is completed, this bit is
turned automatically to OFF.
M8021 ~ M8033 Reserved
M8034 All output disable
All physical switch gear for activating outputs is disabled. How-
ever, for debugging purposes the logical state of these outputs
(D100 ~ D199) can be set, but remain disabled in the actual
module.
M8035 ~ M8039 Reserved

Table 4.6:Special Data Registers (D8020 ~ D8039)

Diagnostic
Device Name Description
D8020 ()Data exchange
status
Data register D8020 contains a status bit for data exchange.
If this is “1”, 32DP-IF is in data exchange mode.
If this is “0”, 32DP-IF is not in data exchange mode.
D8021 ()Swap byte order See note 1.
D8022 ()Length of input
(sent) data in byte The values held in these devices are copied from the input data
length and output data length setting in the DP-master.
D8023 ()Length of output
(received) data in
byte
D8024 ()Baud rate See note 2.
D8025 ()Communication
status See note 3.
D8026 ()Profibus module
ID (PNO ID code)
PNO-Nr.F232 (Hex)
(This number contains the Profibus module ID number for the
32DP-IF.)
D8027 ()Slave address
The slave address is set only by the 32DP-IF’s DIP switches.
The slave address value is 0 to 126. The address change by a
Profibus-DP Class 2 master via the network or by a program-
ming device is not supported.
D8028 Reserved
D8029 () ( )Erro r status See note 4.