FX2N-32DP-IF Profibus-DP Interface Units Appendix B
B-3
B-1-3 Example Setting for FX2N-4AD-PT
For BFM’s definition, ref er to FX2N-4AD-PT User’s Manual.
Table B-3:User Parameter for FX2N
-4AD-PTUsing GSD File User
Parameter
Type Description
Using Programming Tool
Byte No. Setting
Value
(Hex)
Register
No.
Setting
Valu e
(Hex)
Higher/
Lower
Byte
0 00 H User
parameter
for 32DP-IF See section 6.1. D200 0000 H Lower
1 00 H Higher
2F8 H
User parameter
for spe cial
function
block
(FX2N-4AD-
PT)
BFM #30 lower byte: “F8 H” D201 07F8 H Lower
3 07 H BFM #30 higher byte: “07 H” Higher
4 06 H Total length of parameter bytes for this
special function block is 9 bytes (byte
No. 4 ~ 9). D202 0406 H
Lower
5 04 H Example: number of BFM for data
exchanged every cycle is 4
BFMs (BFM #9 ~ #12). Higher
6 09 H Specified exchange, ex. BFM #9 D203 0A09 H Lower
7 0A H Specified exchange, ex. BFM #10 Higher
8 0B H Specified exchange, ex. BFM #11 D204 0C0B H Lower
9 0C H Specified exchange, ex. BFM #12 Higher