Mitsubishi Electronics MUZ-D36NA, U1 MAX. Refrigerant Piping Length and MAX. Height Difference

Models: MUY-D36NA MUZ-D30NA U1 MUY-D30NA MUZ-D36NA

1 44
Download 44 pages 58.83 Kb
Page 10
Image 10

MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE

Model

Refrigerant piping : ft.

 

Piping size O.D : in.

Max. Length

Max. Height difference

Gas

 

Liquid

 

A

B

 

 

 

 

 

MUZ-D30NA

 

 

 

 

 

MUZ-D36NA

100

50

5/8

 

3/8

MUY-D30NA

 

 

 

 

 

 

MUY-D36NA

 

 

 

 

 

Indoor unit

Max. Height

difference

B

Max. length

A

Outdoor unit

ADDITIONAL REFRIGERANT CHARGE (R410A:oz.)

Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.

Model

Outdoor unit

 

 

 

Refrigerant piping length (one way) : ft.

 

 

precharged

25

30

 

40

50

60

70

80

90

100

 

 

MUZ-D30NA

4 lb. 10 oz.

0

2.96

 

8.88

14.80

20.72

26.64

32.56

38.48

44.40

MUZ-D36NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Calculation : X oz. = 2.96/5 oz. / ft. x (Refrigerant piping length (ft.) - 25)

Model

Outdoor unit

 

 

 

Refrigerant piping length (one way) : ft.

 

 

precharged

25

30

 

40

50

60

70

80

90

100

 

 

MUY-D30NA

4 lb.

0

1.08

 

3.24

5.40

7.56

9.72

11.88

14.04

16.20

MUY-D36NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Calculation : X oz. = 1.08/5 oz. / ft. x (Refrigerant piping length (ft.) - 25)

NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.