No. | Symptom | Indication | Abnormal point / Condition | Condition |
| Correspondence | ||
LED1 | LED2 |
| ||||||
|
| (Red) | (Yellow) |
|
|
|
| |
20 |
| Once | Lighting | Primary current protection | The input current exceeds 15 A. | • These symptoms do not mean any abnormality of | ||
| Secondary current protection | The current of the compressor exceeds 15 A. | ||||||
|
|
|
| the product, but check the following points. | ||||
|
|
|
| The indoor gas pipe temperature exceeds 113 °F (45 °C) dur- | • Check if indoor filters are clogged. | |||
21 |
| Twice | Lighting | (MUZ) | ing heating. | • Check if refrigerant is short. | ||
| Defrosting in cooling | The indoor gas pipe temperature falls 37 °F (3 °C) or below | • Check if indoor/outdoor unit air circulation is short | |||||
|
|
|
| cycled. |
| |||
|
|
|
| during cooling. |
| |||
|
|
|
|
|
|
| ||
|
|
|
| Discharge temperature protec- | The discharge temperature exceeds 212 °F (100 °C) during | • Check refrigerant circuit and refrigerant amount. | ||
22 | Outdoor | 3 times | Lighting | • Refer to | "Check of LEV". | |||
tion | operation. | |||||||
| unit oper- |
|
|
|
| • Refer to | "Check of outdoor thermistors". | |
23 | ates. | 4 times | Lighting | Low discharge temperature | The frequency of the compressor is kept 80 Hz or more and | • Refer to | "Check of LEV". | |
| the discharge temperature is kept under 102 °F (39 °C) for | |||||||
| protection | • Check refrigerant circuit and refrigerant amount. | ||||||
|
|
|
| more than 20 minutes. | ||||
|
|
|
|
|
|
| ||
|
|
|
|
|
| • This symptom does not mean any abnormality of | ||
|
|
|
| Cooling | The outdoor heat exchanger temperature exceeds 136 °F (58 | the product, but check the following points. | ||
24 |
| 5 times | Lighting | • Check if indoor filters are clogged. | ||||
| tion | °C) during operation. | • Check if refrigerant is short. | |||||
|
|
|
| |||||
|
|
|
|
|
| • Check if indoor/outdoor unit air circulation is short | ||
|
|
|
|
|
| cycled. |
| |
25 | Outdoor | 9 times | Lighting | Inverter check mode | The unit is operated with emergency operation switch. | – |
| |
| unit oper- |
|
|
|
|
|
| |
|
|
|
|
|
|
| ||
26 | ates | Lighting | Lighting | Normal | – | – |
| |
|
|
|
|
|
|
|
|