The operation frequency does not go up from lowest frequency.

ICheck of HPS

1.Disconnect the connector CN681 in the electronic control P.C. board.

2.Check the resistance of HPS 1 minute after the outdoor unit power supply was turned OFF.

Check the resistance between each terminal.

0 Ω

Reconnect CN681.

Turn ON power supply to the indoor and outdoor unit. 3 minutes later, start EMERGENCY OPERATION.

Is HPS protection displayed immediately after compressor starts?

No

Normal

Infinity Replace HPS.

 

 

Replace the outdoor electronic

Yes

 

control P.C. board.