Mitsubishi Electronics MUZ-D30NA, MUZ-D36NA, MUY-D36NA, U1 Outdoor unit failure mode table

Models: MUY-D36NA MUZ-D30NA U1 MUY-D30NA MUZ-D36NA

1 44
Download 44 pages 58.83 Kb
Page 23
Image 23

3. Outdoor unit failure mode table

MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA

 

 

LED indication

 

 

 

 

The left lamp of OPERA-

Abnormal point

(Outdoor P.C.

 

 

 

Indoor/outdoor

TION INDICATOR lamp

board)

Condition

Correspondence

unit failure mode

(Failure mode / protection)

(Indoor unit)

 

 

 

 

 

recall function

 

LED 1

LED 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Non (Normal)

 

 

 

 

 

 

 

 

 

 

 

 

IPM protection stop or lock protection stop is continuously

• Check the connection of the

 

 

 

 

 

compressor connecting wire.

 

2-time flash

Outdoor power system

Lighting

Lighting

performed 3 times within 1 minute after the compres-

• Refer to 10-5.

"How to check

sor gets started, or converter protection stop or bus-bar

inverter / compressor".

 

 

 

 

voltage protection stop is continuously performed 3 times

• Refer to 10-5.

"Check of

 

 

 

 

within 3 minutes after start-up.

compressor start failure".

 

 

 

 

 

 

• Check the stop valve.

 

 

 

 

 

 

 

 

 

 

Discharge temperature thermistor

Lighting

Once

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost thermistor (MUZ)

Lighting

Once

 

• Refer to 10-5.

"Check of

 

 

 

 

 

 

 

 

Ambient temperature thermistor

Lighting

Twice

 

outdoor thermistors".

 

 

 

 

3-time flash

 

 

 

Thermistor shorts or opens during compressor running.

 

 

Fin temperature thermistor

Lighting

3 times

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.C. board temperature thermistor

Lighting

4 times

 

• Replace the outdoor electronic

 

 

 

control P.C. board.

 

 

 

 

 

 

 

 

Outdoor heat exchanger tempera-

Lighting

9 times

 

• Refer to 10-5.

"Check of

 

 

ture thermistor

 

outdoor thermistors".

 

 

 

 

 

 

 

 

 

 

 

• Reconnect compressor con-

 

 

 

 

 

 

nector.

"How to check

 

 

 

 

Goes

 

• Refer to 10-5.

 

4-time flash

Overcurrent

Once

28 A current flow into intelligent power module.

inverter/ compressor."

out

 

 

 

 

• Refer to 10-5.

"Check of

 

 

 

 

 

 

 

 

 

 

 

 

compressor start failure".

 

 

 

 

 

 

• Check the stop valve.

 

 

 

 

 

Temperature of discharge temperature thermistor exceeds

• Check refrigerant circuit and

 

5-time flash

Discharge temperature

Lighting

Lighting

241 °F (116 °C), compressor stops. Compressor can

refrigerant amount.

restart if discharge temperature thermistor reads 212 °F

• Refer to 10-5.

"Check of

 

 

 

 

(100 °C) or less 3 minutes later.

LEV".

 

 

 

 

 

 

 

 

 

6-time flash

High pressure

Lighting

Lighting

The outdoor heat exchanger temperature exceeds 158 °F

• Check refrigerant circuit and

(70 °C) during cooling or the indoor gas pipe temperature

refrigerant amount.

 

 

 

 

exceeds 158 °F (70 °C) during heating (MUZ).

• Check the stop valve.

 

 

 

 

 

 

 

 

 

Fin temperature

3 times

Goes

The fin temperature exceeds 189 °F (87 °C) during opera-

• Check around outdoor unit.

 

 

 

 

out

tion.

• Check outdoor unit air pas-

 

7-time flash

 

 

 

 

sage.

 

 

 

 

 

 

 

P.C. board temperature

4 times

Goes

The P.C. board temperature exceeds 158 °F (70 °C) during

• Refer to 10-5.

"Check of

 

 

out

operation.

outdoor fan motor".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8-time flash

Outdoor fan motor

Lighting

Lighting

Failure occurs continuously 3 times within 30 seconds

• Refer to 10-5.

"Check of

after the fan gets started.

outdoor fan motor".

 

 

 

 

 

 

 

 

 

 

 

 

9-time flash

Nonvolatile memory data

Lighting

5 times

Nonvolatile memory data cannot be read properly.

• Replace the outdoor electronic

control P.C. board.

 

 

 

 

 

 

 

 

 

The frequency of the compressor is kept 80 Hz or more

• Check refrigerant circuit and

 

 

 

 

 

refrigerant amount.

 

10-time flash

Discharge temperature

Lighting

Lighting

and the discharge temperature is kept under 102 °F (39 °C)

• Refer to 10-5.

"Check of

 

 

 

 

for more than 20 minutes.

LEV".

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication error occurs between the electronic control

• Check the connecting wire

 

Communication error between

 

 

P.C. board and power board for more than 10 seconds.

between outdoor electronic

 

Lighting

6 times

 

control P.C. board and power

 

 

P.C. boards

The communication between boards protection stop is

 

 

 

board.

 

 

 

 

 

continuously performed twice.

 

 

 

 

 

 

A short or open circuit is detected in the current sensor

• Replace the power board.

 

 

 

 

during compressor operating.

 

 

 

Current sensor

Lighting

7 times

 

 

 

11-time flash

Current sensor protection stop is continuously performed

 

 

 

 

 

 

 

 

 

 

 

twice.

 

 

 

 

 

 

Zero cross signal cannot be detected while the compres-

• Check the connecting wire

 

 

 

 

sor is operating.

among electronic control P.C.

 

Zero cross detecting circuit

5 times

Goes out

 

board, noise filter P.C. board

 

 

The protection stop of the zero cross detecting circuit is

and power board.

 

 

 

 

 

 

 

 

 

 

continuously performed 10 times.

 

 

 

 

 

 

 

 

 

 

NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).

23

Page 23
Image 23
Mitsubishi Electronics MUZ-D30NA, MUZ-D36NA, MUY-D36NA, U1, MUY-D30NA service manual Outdoor unit failure mode table