9Switch List

SW

 

Supported

Function

OFF

ON

Remark

 

Channel

 

 

 

 

 

 

 

 

 

 

 

 

 

SW01

1

Channel 1

Use of input contact

No

Yes

Set whether to use the Channel 1 input.

 

2

Channel 2

Use of input contact

No

Yes

Set whether to use the Channel 2 input.

 

3

Channel 3

Use of input contact

No

Yes

Set whether to use the Channel 3 input.

 

4

Channel 4

Use of input contact

No

Yes

Set whether to use the Channel 4 input.

 

5

Unused

 

 

 

Set to OFF

 

6

Unused

 

 

 

Set to OFF

 

7

Unused

 

 

 

Set to OFF

 

8

Unused

 

 

 

Set to OFF

SW02

1

 

Pulse weight value setting:

SW02-1,

SW02-2

 

 

 

SC setting (*1):

OFF

OFF

 

 

 

Channel 1

× 0.1:

OFF

ON

Set 1 pulse of the meter connected to channel 1.

 

 

 

2

 

× 1:

ON

OFF

 

 

 

× 10:

ON

ON

 

 

 

 

 

 

3

 

Pulse weight value setting:

SW02-3,

SW02-4

 

 

 

SC setting (*1):

OFF

OFF

 

 

 

Channel 2

× 0.1:

OFF

ON

Set 1 pulse of the meter connected to channel 2.

 

 

 

4

 

× 1:

ON

OFF

 

 

 

× 10:

ON

ON

 

 

 

 

 

 

5

 

Pulse weight value setting:

SW02-5,

SW02-6

 

 

 

SC setting (*1):

OFF

OFF

 

 

 

Channel 3

× 0.1:

OFF

ON

Set 1 pulse of the meter connected to channel 3.

 

 

 

6

 

× 1:

ON

OFF

 

 

 

× 10:

ON

ON

 

 

 

 

 

 

7

 

Pulse weight value setting:

SW02-7,

SW02-8

 

 

 

SC setting (*1):

OFF

OFF

 

 

 

Channel 4

× 0.1:

OFF

ON

Set 1 pulse of the meter connected to channel 4.

 

 

 

8

 

× 1:

ON

OFF

 

 

 

× 10:

ON

ON

 

 

 

 

 

SW03

1

Unused

 

 

 

Set to OFF

 

2

Unused

 

 

 

Set to OFF

 

3

Unused

 

 

 

Set to OFF

 

4

Unused

 

 

 

Set to OFF

 

5

Unused

 

 

 

Set to OFF

 

6

Unused

 

 

 

Set to OFF

 

7

Unused

 

 

 

Set to OFF

 

8

Unused

 

 

 

Set to OFF

SW06

 

 

 

(Address 10s) 0 to 9 (decimal)

An address from 01 to 50 can be set.

 

 

M-NET address

 

 

 

Set an address that is not the same as that of

SW07

 

 

(Address 1s) 0 to 9 (decimal)

 

 

 

another unit.

SW08

 

 

 

 

 

Only enabled during communication error status

 

 

Communication error status display (error code

Change the switch to ON once

display.

 

1

display)

 

* The communication error status display is

 

 

and then return it to OFF.

 

 

Temporary mask setting

masked for 10 seconds and the contact input

 

 

 

 

 

 

 

 

 

 

status is displayed.

 

2

Unused

 

 

 

Set to OFF

 

3

Unused

 

 

 

Set to OFF

 

4

Unused

 

 

 

Set to OFF

 

5

Unused

 

 

 

Set to OFF

 

6

Unused

 

 

 

Set to OFF

SW09

1

Unused

 

 

 

Set to OFF

 

2

Unused

 

 

 

Set to OFF

Set the dip switches for function selection according to the system to be used.

At the time of shipment, all dip switches are set to OFF and the M-NET address is set to 01.

*1: When using a system controller (G(B)-50A or TG-2000A), select the "SC setting" and set the pulse weight value settings from a system controller. If set to another setting, this dip switch setting is prioritized even when set from a system controller.

*2: The pulse unit of the watt-hour meter being used should be 1 kWh/pulse or less. Note that the apportioning error will increase if a watt-hour meter with large pulse unit is used.

10

Page 11
Image 11
Mitsubishi Electronics PAC-YG60MCA instruction manual Switch List, Supported Function

PAC-YG60MCA specifications

The Mitsubishi Electronics PAC-YG60MCA is an advanced control unit designed for optimizing and managing HVAC systems in commercial and residential settings. Featuring state-of-the-art technology, this model offers seamless integration with Mitsubishi's extensive range of heating and cooling solutions, ensuring enhanced energy efficiency and comfort for users.

One of the standout features of the PAC-YG60MCA is its ability to connect multiple units, allowing for centralized management of up to 60 indoor units simultaneously. This capability simplifies the control process for larger systems, providing users with a comprehensive overview of system performance and enabling easy adjustments to temperature settings, fan speeds, and operation modes based on specific preferences and requirements.

The PAC-YG60MCA utilizes a sophisticated control algorithm that prioritizes energy efficiency without compromising on performance. It incorporates advanced sensor technology, which monitors environmental conditions and adjusts system settings in real time. This not only helps to reduce operational costs but also contributes to environmental sustainability by minimizing energy consumption.

Another significant feature of the PAC-YG60MCA is its user-friendly interface, which includes a clear display and intuitive navigation. Users can easily program schedules, change settings, and monitor system performance through a simple menu structure. Additionally, the unit supports remote access via a smartphone app, allowing users to manage their HVAC systems from virtually anywhere, enhancing convenience and flexibility.

Durability and reliability are also key characteristics of the PAC-YG60MCA. Designed with high-quality materials, it can withstand various environmental conditions, ensuring long-lasting performance. The unit complies with stringent safety standards and undergoes rigorous testing to guarantee its robustness, making it a dependable choice for any HVAC installation.

In summary, the Mitsubishi Electronics PAC-YG60MCA is a cutting-edge control unit that enhances HVAC system management through its extensive features, including the ability to connect multiple units, energy-efficient operation, and user-friendly interface. Its advanced technology and durable design make it a valuable asset for both commercial and residential settings, ensuring optimal comfort while reducing energy costs. This model exemplifies Mitsubishi's commitment to innovation, efficiency, and customer satisfaction in the HVAC industry.