Mitsubishi Electronics PAC-YG60MCA Installation Method Parts to be Procured Locally

Models: PAC-YG60MCA

1 16
Download 16 pages 54.47 Kb
Page 5
Image 5

6Installation Method

6-1. Parts to be Procured Locally

Prepare the following parts to install this device.

Required Part

 

Specification

 

 

 

 

 

Unit fixing screws

M4 screw × 4

 

 

 

Power source: 24 VDC 0.2 A (Minimum loading), SELV circuit, power line with grounding terminal

 

Ripple noise: Lower than 200 mVp-p

 

Power supply for this

Compatible specification

 

Authorized or CE marked products

 

unit

 

Subject to regulations: - IEC60950 (or EN60950)

 

 

 

 

 

- CISPR22/24 (or EN55022/24)

 

 

 

- IEC61000-3-2/3-3 (or EN61000-3-2/3-3)

Power line

Use a sheathed vinyl cord or cable.

 

At least 0.75 mm² (AWG18)

 

 

 

 

Type of the cable: Sheathed vinyl cords or cable which comply with the following specifications or equivalent.

 

• CPEV Φ1.2 mm to Φ1.6 mm • CVVS 1.25 mm² to 2 mm² (AWG16 to 14)

M-NET transmission

* CPEV: PE insulated PVC jacketed shielded communication cable

 

line

* CVVS: PVC insulated PVC jacketed shielded control cable

 

PE: Polyethylene PVC: Polyvinyl choloride

 

 

Power needs to be supplied to the M-NET circuitry of this device. Use an outdoor unit or a separately purchased

 

power supply unit for the transmission line.

 

 

Shows the size of the electric wire (copper wire) that is adapted to the terminal block of this device.

Signal lines

Electric wire size ········· (1) Solid wire: Φ0.65 mm (AWG21) - Φ1.2 mm (AWG16)

 

(2) Stranded wire: 0.75 mm² (AWG18) - 1.25 mm² (AWG16)

 

 

 

 

Single strand: At least Φ0.18 mm

[Parts to be Purchased Separately]

 

 

 

 

 

 

Name

Model

Application

Remark

 

 

 

 

Power supply unit

PAC-SC50KUA

Power supply to the M-NET transmission line

This is not required when power is to be

 

 

 

supplied from an outdoor unit.

[Recommended Pulse Specifications]

Prepare a measuring instrument that measures the type of pulse signals indicated in table below.

Type

 

Specifications

 

 

 

 

 

 

 

 

 

 

 

Output pulse relay

Semiconductor relay method

 

 

 

 

method

 

 

 

 

 

 

 

 

 

 

 

100 ~ 300 ms (100 ms and above)

ON

 

 

 

 

Choose an instrument that outputs non-voltage a-contact

 

 

 

Output pulse width

 

 

 

 

point pulse per each pulse output.

 

 

 

 

 

 

 

100 ~ 300 ms

 

 

 

 

 

 

 

 

 

 

 

 

Watt-hour meter: 0.1 kWh/pulse, 1 kWh/pulse recommended

 

 

 

 

 

Water meter: m3/pulse

 

 

 

 

Pulse unit

Gas meter:

m3/pulse

 

 

 

 

 

Calorimeter:

MJ/pulse

 

 

 

 

* Except for the watt-hour meter, select instruments that take measurements in the appropriate pulse unit.

4

Page 5
Image 5
Mitsubishi Electronics PAC-YG60MCA instruction manual Installation Method Parts to be Procured Locally