4

Gravimeter

Unit

[3] Service tools

Use the below service tools as exclusive tools for R410A refrigerant.
3PART NAMES AND FUNCTIONS

Indoor unit

Emergencyoperation
switch
Front grille
Air inlet
Filter
Air outlet
Louver
Vane
No. Tool name Specifications
1Gauge manifold · Only for R410A
· Use the existing fitting specifications. (UNF1/2)
· Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose · Only for R410A
· Use pressure performance of 5.09MPa·G or over.
3Electronic scale
4Gas leak detector · Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check · Attach on vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon
8Refrigerant recovery equipment

[1] Cautions for service

(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.

[2] Additional refrigerant charge

When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)