036-21544-001 Rev. B (1103)

11 MICROPROCESSOR CONTROL

C.Low Ambient Temperature Switch (LATS) - The purpose of this switch is to extend cooling operation in low outdoor temperatures as low as 25°. The outdoor unit uses a high side pressure switch to cycle the fan. When pressure drops to 165 PSI (+/-10), the switch opens and the fan stops. When pressure rises to 300 (+/- 10), the switch closes and the fan restarts. A jumper is factory installed in place of the low ambient pressure switch. This jumper must be removed when a low ambient accessory kit is installed.

During low ambient cooling operation the indoor unit may initiate an “air defrost” of the indoor coil once during every 16 minutes of continuous cooling operation. This insures that the coil has adequate airflow and should not be considered as a fault.

D.Defrost Sensor Switch - The defrost switch is set to close at 35 degrees (+/-7) and opens at 65 degrees (+/-5). The board is factory set with a 60 minute minimum defrost interval and can be reset to 30 or 90 minutes by moving a jumper. When the defrost sensor closes, the defrost timer begins timing out the compressor run time. Once the timer “times out” (30/60/90 minutes) and the switch is closed the reversing valve is shifted and defrost is accomplished. If the room temperature is satisfied during a defrost cycl, the defrosting will continue until the termination temperature is achieved or 10 minutes has elapsed.

E.Crankcase Heater (CCH) - A crankcase heater is installed into all PUGH heat pump units to protect the compressor. When line voltage is first applied to the outdoor unit, the control will energize the crankcase heater. The control will continue to energize the CCH until the first call for compressor operation. The control never energizes the CCH during compressor operation. The control will energize the CCH thirty minutes after the compressor turns off. It will then cycle the CCH on for 30 minutes and off for 30 minutes repeatedly until the compressor is again turned on.

F.Compressor Contactor (CC) - The compressor contactor is energized with 24VAC when a 12 VDC is input to the out- door unit on control wires 1 and 2 from the indoor unit. This 12 VDC signal is generated and sent from the indoor unit on all calls for compressor operation.

G.Outdoor Fan Motor (ODF) - The outdoor fan motor typically operates at the same time as the compressor. However, the fan may be off while the compressor is operating during low ambient cooling conditions as described previously.

H.Transformer Input (24VAC) - The secondary side of the transformer supplies 24 volts AC to the circuit board on the “24VAC” terminals. This voltage operates the internal circuits of the board and also provides voltage to the compressor contactor when appropriate. The primary side of the transformer is powered with line voltage from terminals marked “L1” and “L2” on the board.

I.Line Voltage - Line voltage is input and output from the circuit board on the terminals marked “L1” and “L2”. There are four terminals marked “L1”. These terminals provide “L1” input to the board and “L1” output to the transformer, crank- case heater and the outdoor fan motor.

There are two terminals marked “L2”. One terminal provides “L2” line voltage input to the board. The other provides “L2” output to the transformer.

J.Anti-Recycle Delay Timer - The control provides an “anti-recycle delay” of three minutes in the cooling mode.

K.Time Shortening - Placing the defrost jumper to the “TEST” position shortens timings of the control to the following values.

1.Anti-Recycle - 36 seconds

2.CCH Cycles - 24 seconds

3.Compressor Run - 1 second

4.Low Pressure Bypass - 12 seconds

L.Last Fault Memory Recall. The control maintains a memory of the last fault that occurred. The last fault code can be recalled by moving the defrost jumper to the “TEST” position and observing the “STATUS” LED display. The control stores only the last fault code. The control will reset the fault code memory when the line voltage to the outdoor unit is turned off.

M.LED Function. The board has four LED’s which provide the following function:

1.“STATUS” LED indicates normal operation or faults as follows:

LED FLASHES

INDICATION OF CONDITION

Off

Normal Operation, no fault, no “call”

Constant on LED

Anti-recycle delay active. If the HPSS or LPS opens, the anti-recycle

will activate for 3 minutes before the fault can be displayed.

 

1 Flash Sequence

Defrost Sensor Closed

2 Flash Sequence

High Pressure Safety Switch Open

3 Flash Sequence

LATS Open

4 Flash Sequence

Low Pressure Safety Switch Open

2.“CCH” LED indicates that the crankcase heater is energized.

3.“2” LED indicates that the indoor unit is calling for compressor operation, 12VDC is present on control wire #2.

30

Mitsubishi Electronics 2003

Page 30
Image 30
Mitsubishi Electronics PUGH42AYB, PUGH36AYB, PUGH24AYB, PUGH18AYB, PUGH30AYB LED Flashes Indication of Condition