036-21544-001 Rev. B (1103)

2 SPECIFICATIONS

PCGH SERIES - HEAT PUMP SYSTEMS

SYSTEM

INDOOR

OUTDOOR

BTU/H

BTUH/H HEAT

SEER

EER*

HSPF

COP*

COOL*

(AUX)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PCGH24GK

PCH24GK

PUGH24AYB

25000

24200

10.00

9.00

7.35

3.10

 

 

 

 

 

 

 

 

 

PCGH30GK

PCH30GK

PUGH30AYB

30200

31000

10.00

9.35

7.6

3.33

 

 

 

 

 

 

 

 

 

PCGH36GK

PCH36GK

PUGH36AYB

35800

36200

10.50

9.65

7.4

3.24

 

 

 

 

 

 

 

 

 

PCGH42GK

PCH42GK

PUGH42AYB

40500

45000

11.50

10.25

7.8

3.35

 

 

 

 

 

 

 

 

 

*Conditions taken at ARI A (95° F outdoor / 80° F DB, 67° F WB indoor) for cooling and ARI high temperature heating test (47° F outdoor / 70° F DB, 60° F WB indoor) for heating. Based on ARI operating conditions. Specifications subject to change without notice.

PKGH SERIES - HEAT PUMP SYSTEMS

SYSTEM

INDOOR

OUTDOOR

BTU/H

BTUH/H HEAT

SEER

EER*

HSPF

COP*

COOL*

(AUX)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKGH18FK3

PKH18FK3

PUGH18AYB

17900

17400

11.50

10.00

7.5

3.38

PKGH24FK3

PKH24FK3

PUGH24AYB

23400

23000

10.50

9.20

7.45

3.10

PKGH30FK3

PKH30FK3

PUGH30AYB

29600

30000

11.00

9.85

7.8

3.44

PKGH36FK3

PKH36FK3

PUGH36AYB

34200

35000

10.70

9.85

7.4

3.22

*Conditions taken at ARI A (95° F outdoor / 80° F DB, 67° F WB indoor) for cooling and ARI high temperature heating test (47° F outdoor / 70° F DB, 60° F WB indoor) for heating. Based on ARI operating conditions. Specifications subject to change without notice.

PLGH SERIES - HEAT PUMP SYSTEMS

SYSTEM

INDOOR

OUTDOOR

BTU/H

BTUH/H HEAT

SEER

EER*

HSPF

COP*

COOL*

(AUX)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLGH18AK

PLH18AK3

PUGH18AYB

19200

19200

10.75

10.00

7.6

3.64

 

 

 

 

 

 

 

 

 

PLGH24AK

PLH24AK3

PUGH24AYB

24400

24200

10.00

8.90

7.25

3.04

 

 

 

 

 

 

 

 

 

PLGH30AK

PLH30AK3

PUGH30AYB

27800

30200

10.00

8.85

7.4

3.18

 

 

 

 

 

 

 

 

 

PLGH36AK

PLH36AK3

PUGH36AYB

35200

36400

10.00

9.45

7.35

3.22

 

 

 

 

 

 

 

 

 

PLGH42AK

PLH42AK3

PUGH42AYB

40000

45000

11.00

9.85

7.5

3.22

 

 

 

 

 

 

 

 

 

*Conditions taken at ARI A (95° F outdoor / 80° F DB, 67° F WB indoor) for cooling and ARI high temperature heating test (47° F outdoor / 70° F DB, 60° F WB indoor) for heating. Based on ARI operating conditions. Specifications subject to change without notice.

ELECTRICAL SPECIFICATIONS - HEAT PUMP UNITS

MODEL

 

PUGH18AYB

PUGH24AYB

PUGH30AYB

PUGH36AYB

PUGH42AYB

Compressor

Locked Rotor Amps1

48

68

82

86

109

 

 

 

 

 

 

Full Load Amps1

9.0

12.8

14.7

16.6

18.3

 

 

 

 

 

 

 

 

Outdoor Fan

Full Load Amps1

0.5

0.5

1.4

1.3

1.3

 

 

 

 

 

 

 

Unit Total

Full Load Amps1

9.5

13.3

16.1

17.9

19.6

 

 

 

 

 

 

 

Max Fuse Size (Amps)

 

20

25

30

35

40

 

 

 

 

 

 

 

Min. Circuit Ampacity

 

11.8

12.8

19.8

22.1

24.2

 

 

 

 

 

 

 

Mitsubishi Electronics 2003

3

Page 3
Image 3
Mitsubishi Electronics PUGH18AYB, PUGH42AYB Specifications, Pcgh Series Heat Pump Systems, Pkgh Series Heat Pump Systems