FX1S Series Programmable Controllers Installation Notes 3

3-4

3.3 General Specifications

Table 3.3: General Specifications

*1 The criterion is shown in IEC61131-2.

*2 Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may

damage the PLC.

Item Description
Operating Temperature 0 to 55 °C (32 to 131 °F)
Storage Temperature -20 to 70 °C (-4 to 158 °F)
Operating Humidity 35 to 85% Relative Humidity, No condensation
Storage Humidity 35 to 90% Relative Humidity, No condensation
Vibration Resistance*1
- Direct Mounting
10 - 57 Hz: 0.075 mm Half Amplitude
57 - 150 Hz: 9.8 m/s2 Acceleration
Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
Vibration Resistance*1
- DIN Rail Mounting
10 - 57 Hz: 0.035 mm Half Amplitude
57 - 150 Hz: 4.9 m/s2 Acceleration
Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
Shock Resistance*1 147m/s2 Acceleration, Action Time: 11 ms
3 times in each direction X, Y, and Z
Noise Immunity 1000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator
Dielectric
Withstand Voltage
AC PSU: 1500 VAC > 1 min., tested between all points, terminals, and ground
DC PSU: 500 VAC > 1 min., tested between all points, terminals and ground
Insulation Resistance 5 M > at 500 V DC, tested between power terminals and ground
Ground Grounding resistance 100 or less
Working atmosphere Free from corrosive or flammable gas and excessive conductive dust
Working altitude <2000m*2
Certification UL/cUL (UL508)
EC Directive EMC(EN61000-6-2, EN50081-2), LVD(EN61010-1)