FX1S Series Programmable Controllers Installation Notes 3
3-10
3.7 Termination of Screw Terminals
Terminal screws should be tightened to between 0.5 to 0.8 Nm. Terminal screws must be
secured to prevent a loose connection thus avoiding a malfunction. Failure to do so may cause
equipment failures or malfunctions.
The terminal screws for the FX1S Series PLC are M3.0. The crimp style ter minal (see Figure
3.4 and 3.6) is suitable for use with these screws and should be fitted to the cable for wiring.
When installing 1 or 2 crimp terminals to a terminal, see explanation Figure 3.5 and 3.7.
However, 3 crimp terminals or more should not be installed to a single terminal.