Error Code Abnormal point and detection method

Cause

Countermeasure

 

Indoor/outdoor unit communication

1 Contact failure, short circuit or, Check LED display on the outdoor control cir-

 

error (Signal receiving error)

miswiring (converse wiring) of

cuit board. (Connect A-control service tool,

 

1 Abnormal if indoor controller board

indoor/outdoor unit connecting

PAC-SK52ST.)

 

cannot receive any signal normally for 6

Refer to EA-EC item if LED displays EA-EC.

 

wire

 

minutes after turning the power on.

1 Check disconnection or looseness of indoor/

 

2 Defective transmitting receiving

 

2 Abnormal if indoor controller board

circuit of indoor controller board

outdoor unit connecting wire of indoor unit or

 

cannot receive any signal normally for 3

outdoor unit.

 

3 Defective transmitting receiving

E6

minutes.

Check all the units in case of twin indoor

3 Consider the unit as abnormal under the

circuit of indoor controller board

unit system.

 

 

following condition: When 2 or more

4 Noise has entered into indoor/

2-4Turn the power off, and on again to

 

indoor units are connected to 1

outdoor unit connecting wire.

check. If abnormality generates again,

 

outdoor unit, indoor controller board

 

replace indoor controller board or outdoor

 

cannot receive a signal for 3 minutes

 

controller circuit board.

 

from outdoor controller circuit board, a

 

Other indoor controller board may have

 

signal which allows outdoor controller

 

defect in case of twin indoor unit system.

 

circuit board to transmit signals.

 

 

 

 

 

 

Indoor/outdoor unit communication

1 Defective transmitting receiving 1-3Turn the power off, and on again to

 

error (Transmitting error)

circuit of indoor controller board

check. If abnormality generates again,

E7

Abnormal if “1” receiving is detected 30

2 Noise has entered into power

replace indoor controller board.

times continuously though indoor controller

supply.

 

 

 

 

board has transmitted “0”.

3 Noise has entered into outdoor

 

 

 

control wire.

 

 

 

 

 

 

Indoor controller board

1 Defective indoor controller

1 Replace indoor controller board.

Fb

Abnormal if data cannot be normally read

board

 

from the nonvolatile memory of the indoor

 

 

 

 

 

 

controller board.

 

 

 

 

 

 

 

Remote controller control board

1 Defective remote controller

1 Replace remote controller.

1Abnormal if data cannot be normally read from the nonvolatile memory of the

E1

remote controller control board.

 

 

(Error code: E1)

 

 

or

 

 

 

 

 

E2

2 Abnormal if the clock function of remote

 

 

 

controller cannot be normally operated.

 

 

 

(Error code: E2)

 

 

 

 

 

 

 

Forced compressor stop

1 Drain pump trouble

1 Check the drain pump.

 

(due to water leakage abnormality)

 

 

 

1 When the intake temperature subtracted

2 Drain defective

2 Please confirm whether water can be

 

with liquid pipe temperature is less than

· Drain pump clogging

drained.

 

-10:(14˚F), drain sensor detects

· Drain pipe clogging

 

 

whether it is soaked in the water or not

 

 

 

at the interval of 90 seconds. (Drain

3 Open circuit of drain sensor

3 Confirm the resistance of the drain sensor.

 

pump will start operating when the drain

side heater

 

 

sensor detects to be soaked in the

 

 

 

water.)

4 Contact failure of drain sensor 4 Check the connector contact failure.

 

2 The unit has a water leakage abnormality

connector

 

 

when the following conditions, a and b,

 

 

 

are satisfied while the above-mentioned

5 Dew condensation on drain

5 Check the drain sensor leadwire mounted.

 

detection is performed.

sensor

Check the filter clogging.

PA

a) The drain sensor detects to be

· Drain water trickles along

 

soaked in the water 10 times in a row.

lead wire.

 

(2502)

 

b) The intake temperature subtracted

· Drain water waving due to filter

 

(2500)

 

with liquid pipe temperature is detect-

clogging

 

 

 

 

ed to be less than -10:(14˚F) for a

 

 

 

total of 30 minutes. (When the drain

6 Extension piping connection

6 Check the piping connection.

 

sensor detects to be NOT soaked in

difference at twin system

 

 

the water, the detection record of a

 

 

 

and b will be cleared.)

 

 

 

3 The drain sensor detection is performed

7 Miswiring of indoor/ outdoor

7 Check the indoor/ outdoor connecting wires.

 

in operations other than cooling. (When

connecting at twin system

 

 

the unit stops operating, during heating

 

 

 

or fan operation, when the unit stops

 

 

 

because of some abnormality)

8 Room temperature thermistor /

8 Check the room temperature display of

 

*Once the water leakage abnormality is

liquid pipe temperature thermis-

remote controller.

 

detected, abnormality state will not be

tor detection is defective.

Check the indoor liquid pipe temperature

 

released until the main power is reset.

 

display of outdoor controller board.

21