9. Additional refrigerant charge

At the time of shipping, the outdoor unit is charged with the refrigerant. As this charge does not include the amount needed for extended piping, additional charg- ing for each refrigerant line will be required on site. In order that future servicing may be properly provided, always keep a record of the size and length of each refrigerant line and the amount of additional charge by writing it in the space pro- vided on the outdoor unit.

9.1.Calculation of additional refrigerant charge

Calculate the amount of additional charge based on the length of the piping extension and the size of the refrigerant line.

Use the table to the below as a guide to calculating the amount of additional charging and charge the system accordingly.

If the calculation results in a fraction of less than 0.1 kg [4oz], round up to the next 0.1 kg [4oz]. For example, if the result of the calculation was 11.38 kg [402oz], round the result up to 11.4 kg [404oz].

<Additional Charge>

After evacuation and refrigerant charge, ensure that the handle is fully open. If operating with the valve closed, abnormal pressure will be imparted to the high- or low-pressure side of the refrigerant circuit, giving damage to the com- pressor, four-way valve, etc.

Determine the amount of additional refrigerant charge by using the formula, and charge refrigerant additionally through the service port after completing piping connection work.

After completing work, tighten the service port and cap securely not to gener- ate gas leak.

Flare machining dimension for systems using R410A is larger than that for systems using other types of refrigerant in order to increase the air tightness.

Refer to the table on the below for flare machining dimensions, and follow the regulations set forth by the local authorities. Seal off the opening of the pipe with a closure material (not supplied) to keep small animals from entering the pipe if that is a concern.

flare machining dimension (mm)

 

 

 

outer diameter

size in inches

dimension A

 

R410A

 

 

 

GB

Additional refrigerant charge

(kg) [oz]

=

+

Liquid pipe size Total length of ø19.05 [3/4]

(m)0.29 (kg/m) (ft) 3.1 (oz/ft)

Liquid pipe size Total length of ø9.52 [3/8]

(m)0.06 (kg/m) (ft) 0.65 (oz/ft)

+

+

Liquid pipe size Total length of ø15.88 [5/8]

(m)0.2 (kg/m) (ft) 2.15 (oz/ft)

Liquid pipe size Total length of ø6.35 [1/4]

(m)0.024 (kg/m) (ft) 0.26 (oz/ft)

Liquid pipe size

+Total length of ø12.7 [1/2]

(m)0.12 (kg/m) (ft) 1.29 (oz/ft)

+α

 

ø6.35

1/4"

9.1

A

ø9.52

3/8"

13.2

 

ø12.7

1/2"

16.6

 

ø15.88

5/8"

19.7

 

ø19.05

3/4"

24.0

flare nut size (mm)

 

 

 

 

outer diameter

size in inches

dimension B

 

R410A

 

 

 

 

ø6.35

1/4"

17.0

 

ø9.52

3/8"

22.0

 

ø12.7

1/2"

26.0

<Example>[Fig. 8.2.1] (P.3)

 

 

 

 

 

Indoor No.1: 48

A: ø12.7 [1/2]

40 m [131ft]

a: ø9.52 [3/8]

10 m

[32ft]

At the

No.2: 36

B: ø9.52 [3/8]

10 m [32ft]

b: ø9.52 [3/8]

5 m

[16ft]

No.3: 15

C:ø9.52 [3/8]

15 m [49ft]

c: ø6.35 [1/4]

10 m

[32ft]

conditions

No.4: 12

D:ø9.52 [3/8]

10 m [32ft]

d: ø6.35 [1/4]

10 m

[32ft]

below:

No.5: 24

 

 

e: ø9.52 [3/8]

10 m

[32ft]

 

The total length of each liquid line is as follows: ø12.7 [1/2]: A = 40 [131] = 40 m [131ft] ø9.52 [3/8]: B + C + D + a + b + e

=10 [32] + 15 [49] + 10 [32] + 10 [32] + 5 [16] + 10 [32] = 60 m [193ft]

ø6.35 [1/4]: c + d = 10 [32] + 10 [32] = 20 m [64ft] Therefore,

<Calculation example> Additional refrigerant charge

=40 [131] 0.12 [1.29] + 60 [193] 0.06 [0.65] + 20 [64] 0.024 [0.26] + 2.5 [89]

=11.4 kg [400oz]

Value of α

Total capacity of connecting indoor units

α

Models 31 to 60

1.5 kg [53oz]

Models 61 to 126

2.0 kg [71oz]

Models 127 to 180

2.5 kg [89oz]

Models 181 to 234

3.0 kg [106oz]

Models 235 to 264

4.0 kg [142oz]

Models 265 to 366

5.0 kg [177oz]

9.2. Precautions concerning piping connec- tion and valve operation

Conduct piping connection and valve operation accurately.

The gas side connecting pipe is assembled in factory before shipment.

1For brazing to the connecting pipe with flange, remove the connecting pipe with flange from the ball valve, and braze it outside of the unit.

2During the time when removing the connecting pipe with flange, remove the seal attached on the rear side of this sheet and paste it onto the flange surface of the ball valve to prevent the entry of dust into the valve.

3The refrigerant circuit is closed with a round, close-packed packing upon shipment to prevent gas leak between flanges. As no operation can be done under this state, be sure to replace the packing with the hollow pack- ing attached at the piping connection.

4At the mounting of the hollow packing, wipe off dust attached on the flange sheet surface and the packing. Coat refrigerating machine oil (Ester oil, ether oil or alkylbenzene [small amount]) onto both surfaces of the pack- ing.

[Fig. 9.2.1] (P.4)

AClose-packed packing

BHollow packing

B

ø15.88

5/8"

29.0

 

ø19.05

3/4"

36.0

[Fig. 9.2.2] (P.4)

<A> [Ball valve (gas side/flanged type)]

<B> [Ball valve (liquid side)]

<C> [Ball valve (gas side/flared type)]

<D>This figure shows the valve in the fully open state.

AValve stem

[Fully closed at the factory, when connecting the piping, when evacuating, and when charging additional refrigerant. Open fully after the operations above are completed.]

BStopper pin [Prevents the valve stem from turning 90° or more.]

CPacking (Accessory)

[Manufacturer: Nichiasu corporation]

[Type: T/#1991-NF]

DConnecting pipe (Accessory)

[Use packing and securely install this pipe to the valve flange so that gas leakage will not occur. (Tightening torque : 40 N·m [400 kg·cm]) Coat both surfaces of the packing with refrigerating machine oil. (Ester oil, ether oil or alkylbenzene [small amount])]

EOpen (Operate slowly)

FCap, copper packing

[Remove the cap and operate the valve stem. Always reinstall the cap after op- eration is completed. (Valve stem cap tightening torque: 23 ~ 27 N·m [230 ~ 270 kg·cm])]

GService port

[Use this port to evacuate the refrigerant piping and add an additional charge at the site.

Open and close the port using a double-ended wrench.

Always reinstall the cap after operation is completed. (Service port cap tightening torque: 12 ~ 15 N·m [120 ~ 150 kg·cm])]

HFlare nut

[Tightening torque: Refer to the chart on the next page. Loosen and tighten this nut using a double-ended wrench.

Coat the flare contact surface with refrigerating machine oil (Ester oil, ether oil or alkylbenzene [small amount])]

Iø9.52 [3/8] (PUHY-P72 ~ P108) ø12.7 [1/2] (PUHY-P126, PUHY-P144) ø15.88 [5/8] (PUHY-P168 ~ P234)

[With P96 and P108 types, when the piping length is long and the pipe size is increased to ø12.7 [1/2], connect to a ø9.52 [3/8] pipe first and then connect to a ø12.7 [1/2] pipe. (The maximum allowable length of the ø9.52 [3/8] pipe is 1 m [39-3/8in].)]

Jø22.2 [7/8] (PUHY-P96 ~ P108) ø28.58 [1-1/8] (PUHY-P126 ~ P234)

[With P96 and P108 types, when the piping length is long and the pipe size is increased to ø12.7 [1/2], connect to a ø9.52 [3/8] pipe first and then connect to a ø12.7 [1/2] pipe.(The maximum allowable length of the ø9.52 [3/8] pipe is 1 m [39-3/8in].)]

KField piping

[Braze to the connecting pipe. (When brazing, use unoxidized brazing.)]

Lø19.05 [3/4] (PUHY-P72)

10

Page 10
Image 10
Mitsumi electronic PUHY-P-TGMU-A Additional refrigerant charge, Calculation of additional refrigerant charge

PUHY-P-TGMU-A specifications

The Mitsumi Electronic PUHY-P-TGMU-A is a cutting-edge multi-split air conditioning system that adopts advanced technologies to enhance indoor comfort and energy efficiency. Designed for both residential and commercial use, this unit stands out due to its innovative features and remarkable performance capabilities.

One of the key characteristics of the PUHY-P-TGMU-A is its ability to effectively cool or heat multiple spaces simultaneously. With a capacity range that meets the demands of diverse environments, this system can seamlessly cater to larger installations. This makes it ideal for office buildings, retail spaces, or homes with multiple rooms requiring climate control.

The unit is equipped with inverter technology, which allows for variable speed operation of the compressor. This not only results in significant energy savings but also provides a stable temperature and optimal comfort levels. The inverter technology adjusts the power consumption based on the cooling or heating requirements in real-time, thereby reducing energy costs and increasing overall efficiency.

Another outstanding feature is the advanced air filtration system. The PUHY-P-TGMU-A incorporates a combination of pre-filters and HEPA filters that effectively reduce airborne particles, allergens, and pollutants. This ensures that the air circulated within the environment remains clean and healthy, making it an excellent choice for those with respiratory sensitivities.

In addition, the unit comes with smart connectivity options. Users can control the system remotely through a smartphone app, allowing for seamless adjustments to settings from anywhere at any time. This smart technology not only enhances convenience but also enables users to monitor energy consumption and adjust schedules to maximize efficiency when spaces are unoccupied.

Thermal management technologies integrated into the PUHY-P-TGMU-A ensure rapid and effective heat exchange, further improving performance. Its sleek design and compact dimensions allow for flexible installation, making it suitable for a variety of architectural styles.

The PUHY-P-TGMU-A is not only about performance; it emphasizes quiet operation too. The design minimizes noise levels, ensuring that the atmosphere remains tranquil even during peak operation.

In summary, the Mitsumi Electronic PUHY-P-TGMU-A combines sophisticated technology, energy efficiency, and user-friendly features to create a versatile and highly effective climate control solution. Whether for personal or business use, this multi-split air conditioning system proves to be an investment in comfort and innovation.