Appropriate tightening torque by torque wrench:

Copper pipe external dia. (mm [in])

Tightening torque (N·m/kg·cm)

ø6.35 [1/4]

 

 

14 to 18

/ 140 to 180

ø9.52 [3/8]

 

 

35 to 42

/ 350 to 420

ø12.7 [1/2]

 

 

50 to 57.5 / 500 to 575

ø15.88 [5/8]

 

 

75 to 80

/ 750 to 800

ø19.05 [3/4]

 

100 to 140

/ 1000 to 1400

Tightening angle standard:

 

 

 

 

 

 

 

 

 

Pipe diameter (mm [in])

 

Tightening angle (°)

 

ø6.35 [1/4], ø9.52 [3/8]

 

60 to 90

 

 

 

ø12.7 [1/2], ø15.88 [5/8]

 

30 to 60

 

 

 

ø19.05 [3/4]

 

20 to 35

 

 

 

[Fig. 9.2.3] (P.4)

Note:

If a torque wrench is not available, use the following method as a standard: When you tighten the flare nut with a wrench, you will reach a point where the tightening torque will abruptly increase. Turn the flare nut beyond this point by the angle shown in the table above.

Caution:

Always remove the connecting pipe from the ball valve and braze it out- side the unit.

-Brazing the connecting pipe while it is installed will heat the ball valve and cause trouble or gas leakage. The piping, etc. inside the unit may also be burned.

Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerat- ing machine oil to coat flares and flange connections.

-The refrigerating machine oil will degrade if it is mixed with a large amount of mineral oil.

Keep the ball valve closed until refrigerant charging to the pipes to be added on site has been completed. Opening the valve before charging the refrigerant may result in unit damage.

Do not use a leak detection additive.

9.3. Airtight test, evacuation, and refrigerant charging

1Airtight test

Perform with the ball valve of the outdoor unit closed, and pressurize the con- nection piping and the indoor unit from the service port provided on the ball valve of the outdoor unit. (Always pressurize from both the high press pipe and the low press pipe service ports.)

[Fig. 9.3.1] (P.4)

A Nitrogen gas

B To indoor unit

C System analyzer

D

Lo knob

E

Hi knob

F

Ball valve

G

Liquid pipe

H

Gas pipe

I

Outdoor unit

JService port

Observe the following restrictions when conducting an air tightness test to prevent negative effects on the refrigerating machine oil. Also, with nonazeotropic refriger- ant (R410A), gas leakage causes the composition to change and affects perform- ance. Therefore, perform the airtightness test cautiously.

GB

 

Airtight test procedure

Restriction

 

 

1. Nitrogen gas pressurization

• If a flammable gas or air (oxygen) is used as the pressurization

(1)

After pressurizing to the design pressure (4.15 MPa [602psi]) using nitrogen gas, allow it to

gas, it may catch fire or explode.

 

stand for about one day. If the pressure does not drop, airtightness is good.

 

 

However, if the pressure drops, since the leaking point is unknown, the following bubble test

 

 

may also be performed.

 

(2)

After the pressurization described above, spray the flare connection parts, brazed parts, flanges,

 

 

and other parts that may leak with a bubbling agent (Kyuboflex, etc.) and visually check for

 

 

bubbles.

 

(3)

After the airtight test, wipe off the bubbling agent.

 

 

 

2. Pressurization using refrigerant gas and nitrogen gas

• Do not use a refrigerant other than that indicated on the unit.

(1)

Pressurizing to a gas pressure of approximately 0.2 MPa [29psi], pressurize to the design

• Sealing with gas from a cylinder will cause the composition of

 

pressure (4.15 MPa [602psi]) using nitrogen gas.

the refrigerant in the cylinder to change.

 

However, do not pressurize at one time. Stop during pressurization and check that the pres-

• Use a pressure gauge, charging hose, and other parts especially

 

sure does not drop.

for R410A.

(2)

Check for gas leaks by checking the flare connection parts, brazed parts, flanges, and other

• An electric leak detector for R22 cannot detect leaks of R410A.

 

parts which may leak using an R410A compatible electric leak detector.

• Do not use a haloid torch. (Leaks cannot be detected.)

(3)

This test may be used together the with bubble type gas leak test.

 

 

 

 

Caution:

Only use refrigerant R410A.

-The use of other refrigerant such as R22 or R407C, which contains chlorine, will deteriorate the refrigerating machine oil or cause the compressor to malfunction.

2Evacuation

Evacuate with the ball valve of the outdoor unit closed and evacuate both the connection piping and the indoor unit from the service port provided on the ball valve of the outdoor unit using a vacuum pump. (Always evacuate from the service port of both liquid pipe and gas pipe.) After the vacuum reaches 650 Pa [abs] [0.0943 psi/5Torr], continue evacuation for at least one hour or more.

*Never perform air purging using refrigerant.

[Fig. 9.3.2] (P.4)

A System analyzer

B Lo knob

C Hi knob

D Ball valve

E Liquid pipe

F Gas pipe

G Service port

H Three-way joint

I Valve

J

Valve

K

R410A cylinder

L

Scale

M

Vacuum pump

N

To indoor unit

O

Outdoor unit

Note:

Always add an appropriate amount of refrigerant. Also always seal the system with liquid refrigerant.Too much or too little refrigerant will cause trouble.

Use a gauge manifold, charging hose, and other parts for the refrigerant indicated on the unit.

Use a gravimeter. (One that can measure down to 0.1 kg [3oz].)

Use a vacuum pump with a reverse flow check valve.

(Recommended vacuum gauge: ROBINAIR 14830A Thermistor Vacuum Gauge)

Also use a vacuum gauge that reaches 65 Pa [abs] [0.00943 psi/0.5Torr] or below after operating for five minutes.

3Refrigerant Charging

Since the refrigerant used with the unit is nonazerotropic, it must be charged in the liquid state. Consequently, when charging the unit with refrigerant from a cylinder, if the cylinder does not have a syphon pipe, charge the liquid refriger- ant by turning the cylinder upside-down as shown in Fig.9.3.3. If the cylinder has a syphon pipe like that shown in the picture on the right, the liquid refriger- ant can be charged with the cylinder standing upright. Therefore, give careful attention to the cylinder specifications. If the unit should be charged with gas refrigerant, replace all the refrigerant with new refrigerant. Do not use the re- frigerant remaining in the cylinder.

[Fig. 9.3.3] (P.4)

A Syphon pipe

B In case of the cylinder having no syphon pipe.

9.4. Thermal insulation of refrigerant piping

Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness heat-resistant polyethylene, so that no gap is observed in the joint between indoor unit and insulating material, and insulating materials themselves. When insulation work is insufficient, there is a possibility of condensation drip, etc. Pay special attention to insulation work to ceiling plenum.

[Fig. 9.4.1] (P.5)

A

Steel wire

B

Piping

C

Asphaltic oily mastic or asphalt

D

Heat insulation material A

EOuter covering B

Heat

Glass fiber + Steel wire

insulation

Adhesive + Heat - resistant polyethylene foam + Adhesive tape

material A

 

 

 

 

 

Outer

Indoor

Vinyl tape

Floor exposed

Water-proof hemp cloth + Bronze asphalt

covering B

Outdoor

Water-proof hemp cloth + Zinc plate + Oily paint

 

 

 

 

11

Page 11
Image 11
Mitsumi electronic PUHY-P-TGMU-A Airtight test, evacuation, and refrigerant charging, Only use refrigerant R410A

PUHY-P-TGMU-A specifications

The Mitsumi Electronic PUHY-P-TGMU-A is a cutting-edge multi-split air conditioning system that adopts advanced technologies to enhance indoor comfort and energy efficiency. Designed for both residential and commercial use, this unit stands out due to its innovative features and remarkable performance capabilities.

One of the key characteristics of the PUHY-P-TGMU-A is its ability to effectively cool or heat multiple spaces simultaneously. With a capacity range that meets the demands of diverse environments, this system can seamlessly cater to larger installations. This makes it ideal for office buildings, retail spaces, or homes with multiple rooms requiring climate control.

The unit is equipped with inverter technology, which allows for variable speed operation of the compressor. This not only results in significant energy savings but also provides a stable temperature and optimal comfort levels. The inverter technology adjusts the power consumption based on the cooling or heating requirements in real-time, thereby reducing energy costs and increasing overall efficiency.

Another outstanding feature is the advanced air filtration system. The PUHY-P-TGMU-A incorporates a combination of pre-filters and HEPA filters that effectively reduce airborne particles, allergens, and pollutants. This ensures that the air circulated within the environment remains clean and healthy, making it an excellent choice for those with respiratory sensitivities.

In addition, the unit comes with smart connectivity options. Users can control the system remotely through a smartphone app, allowing for seamless adjustments to settings from anywhere at any time. This smart technology not only enhances convenience but also enables users to monitor energy consumption and adjust schedules to maximize efficiency when spaces are unoccupied.

Thermal management technologies integrated into the PUHY-P-TGMU-A ensure rapid and effective heat exchange, further improving performance. Its sleek design and compact dimensions allow for flexible installation, making it suitable for a variety of architectural styles.

The PUHY-P-TGMU-A is not only about performance; it emphasizes quiet operation too. The design minimizes noise levels, ensuring that the atmosphere remains tranquil even during peak operation.

In summary, the Mitsumi Electronic PUHY-P-TGMU-A combines sophisticated technology, energy efficiency, and user-friendly features to create a versatile and highly effective climate control solution. Whether for personal or business use, this multi-split air conditioning system proves to be an investment in comfort and innovation.