3. Specifications
|
| Model |
| |||||
|
| Noise level (50/60 Hz) | 56 dB<A> | 57 dB<A> | 60 dB<A> | 61 dB<A> | 61 dB<A> | |
|
| External static pressure |
|
| 0 Pa |
|
| |
|
| Indoor units | Total capacity |
|
| 50 ~130 % |
|
|
|
|
| Model |
|
| 06 ~ 96 |
|
|
|
|
| Quantity | 1 ~ 13 | 1 ~ 16 | 1 ~ 19 | 1 ~ 20 | 1 ~ 22 |
|
| Operation | Standard type | Cooling mode: – 5 °CDB ~ 43 °CDB [23 °FDB ~ 109 °FDB] (0 °CDB ~ 43 °CDB [32°FDB ~ 109 °FDB] with outdoor unit at lower position) | ||||
|
| temperature |
| Heating mode: – 20 °CWB ~ 15.5 °CWB [– 4 °FWB ~ 60 °FWB] |
|
| ||
|
|
| Fresh air intake | Cooling mode: 21 °CDB ~ 43 °CDB [70 °FDB ~ 109 °FDB] |
|
| ||
|
|
| type | Heating mode: – 12.5 °CWB ~ 20 °CWB [10 °FWB ~ 68 °FWB] |
|
| ||
|
|
|
|
|
|
|
|
|
|
| Model |
| |||||
|
| Noise level (50/60 Hz) | 61 dB<A> | 62 dB<A> | 62 dB<A> | 62.5 dB<A> | 63 dB<A> | |
|
| External static pressure |
|
| 0 Pa |
|
| |
|
| Indoor units | Total capacity |
|
| 50 ~130 % |
|
|
|
|
| Model |
|
| 06 ~ 96 |
|
|
|
|
| Quantity | 1 ~ 24 | 1 ~ 24 | 1 ~ 24 | 1 ~ 32 | 1 ~ 32 |
|
| Operation | Standard type | Cooling mode: – 5 °CDB ~ 43 °CDB [23 °FDB ~ 109 °FDB] (0 °CDB ~ 43 °CDB [32°FDB ~ 109 °FDB] with outdoor unit at lower position) | ||||
|
| temperature |
| Heating mode: – 20 °CWB ~ 15.5 °CWB [– 4 °FWB ~ 60 °FWB] |
|
| ||
|
|
| Fresh air intake | Cooling mode: 21 °CDB ~ 43 °CDB [70 °FDB ~ 109 °FDB] |
|
| ||
GB |
|
|
|
| ||||
|
| type | Heating mode: – 12.5 °CWB ~ 20 °CWB [10 °FWB ~ 68 °FWB] |
|
| |||
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
4. Confirmation of parts attached
|
|
|
|
| (Unit : mm [in]) |
|
| 1 Conduit mounting plate (ø53 | 2 Conduit mounting plate (ø46 | 3 Conduit mounting plate (ø33 | 4 Conduit mounting plate (ø27 |
Model | P72 | – | – | 1 pc. | 1 pc. |
| P96 ~ P108 | – | – | 1 pc. | 1 pc. |
| P126 ~ P234 | 1 pcs. | 1 pc. | – | – |
|
| 5 Tapping screw M4 | 6 Connecting pipe (Flare) | 7 Connecting pipe (Flange) | 8 Packing (inside ø23 [29/32], |
|
|
|
|
| outsideø35 |
Model | P72 | 2 pcs. | 1 pc. | – | – |
| P96 ~ P108 | 2 pcs. | – | 1 pc. | 1 pc. |
| P126 ~ P234 | 2 pcs. | – | 1 pc. | 1 pc. |
5. Space required around unit
[Fig. 5.0.1] (P.2)
<A> Top view |
|
| <B> Side view |
<C> When there is little space up to an obstruction | |||
A Front | B No restrictions on wall height (left and right) | ||
C Air outlet guide (Procured at the site) | D Must be open | ||
E Wall height (H) | F No restrictions on wall height | ||
| (Unit : mm [in]) |
| |
L1 | L2 |
|
|
450 | 100 |
|
|
(4) When unit is surrounded by walls
Note:
•Wall heights “H” of the front and the back sides shall be lower than either the front or the back panel.
•If the panel height is exceeded, add the “h” dimension of the Fig. 5.0.1 to L1 and L2.
(Unit : mm [in])
L1L2
450
(1)Basic space required
(2)When there is an obstruction above the unit
(3)When inlet air enters from right and left sides of unit
•Wall heights “H” of the front and the back sides shall be within total height of unit.
•When wall height “H” exceeds total height of unit, add “h” dimension to L1 and L2 of the Fig. 5.0.1.
“h” = wall height “H’” – total height of unit
Example: When the “h” dimension is 100 mm
the L1 dimension becomes 450
(5) Collective installation and continuous installation
•Space required for collective installation and continuous installation:
When installing several units, provide the space between each block consider- ing passage for air and people.
•Open in two directions.
•In case of wall height “H” exceeds total height of unit, add “h” dimension (h = wall height “H’” – total height of unit) to * marked dimension.
6. Lifting method
•If there is a wall at both the front and the rear of the unit, install up to four units (Every three units in the case of P168 ~ P234.) consecutively in the side direc- tion and provide a space of 1000 mm
[Fig. 6.0.1] (P.2)
Caution:
Be very careful to carry product.
-Do not have only one person to carry product if it weighs more than 20 kg [46LBS].
-PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
-Do not touch heat exchanger fins with your bare hands. Otherwise you may cut your hands.
-Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
-When carrying outdoor unit, be sure to support it at four points. Carrying with
8