Thickness of wire for main power supply, On/Off capacities
<Power soure : 208 V> |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Minimum wire thickness (mm2/AWG) | Switch (A) |
| Breaker for | Breaker for current leakage | ||||
|
|
| Main cable | Branch | Ground | Capacity |
| Fuse | wiring (NFB) |
|
|
|
| P72 | 8.4/8 | – | 8.4/8 | 40 |
| 40 | 40 | 40 | A 100 mA 0.1 sec. or less |
|
| P96 | 13.3/6 | – | 13.3/6 | 50 |
| 50 | 50 | 50 | A 100 mA 0.1 sec. or less |
|
| P108 | 13.3/6 | – | 13.3/6 | 50 |
| 50 | 50 | 50 | A 100 mA 0.1 sec. or less |
|
| P126 | 21.2/4 | – | 21.2/4 | 60 |
| 60 | 60 | 60 | A 100 mA 0.1 sec. or less |
Outdoor unit |
| P144 | 33.6/2 | – | 33.6/2 | 75 |
| 75 | 75 | 75 | A 100 mA 0.1 sec. or less |
| P168 | 33.6/2 | – | 33.6/2 | 75 |
| 75 | 75 | 75 | A 100 mA 0.1 sec. or less | |
|
|
| |||||||||
|
| P192 | 42.4/1 | – | 42.4/1 | 100 |
| 100 | 100 | 100 A 100 mA 0.1 sec. or less | |
|
| P204 | 42.4/1 | – | 42.4/1 | 100 |
| 100 | 100 | 100 A 100 mA 0.1 sec. or less | |
|
| P216 | 42.4/1 | – | 42.4/1 | 100 |
| 100 | 100 | 100 A 100 mA 0.1 sec. or less | |
|
| P234 | 53.5/1/0 | – | 53.5/1/0 | 125 |
| 125 | 125 | 125 A 100 mA 0.1 sec. or less | |
Indoor unit |
| 1.5 | 1.5 | 1.5 | 16 |
| 16 | 20 | 20 | A 30 mA 0.1 sec. or less |
|
| <Power soure : 230 V> |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Minimum wire thickness (mm2/AWG) | Switch (A) |
| Breaker for | Breaker for current leakage | ||||
|
|
|
|
| Main cable | Branch | Ground | Capacity |
| Fuse | wiring (NFB) |
|
|
|
|
|
| P72 | 8.4/8 | – | 8.4/8 | 40 |
| 40 | 40 | 40 | A 100 mA 0.1 sec. or less |
|
|
|
| P96 | 13.3/6 | – | 13.3/6 | 50 |
| 50 | 50 | 50 | A 100 mA 0.1 sec. or less |
|
|
|
| P108 | 13.3/6 | – | 13.3/6 | 50 |
| 50 | 50 | 50 | A 100 mA 0.1 sec. or less |
GB |
|
|
| P126 | 21.2/4 | – | 21.2/4 | 60 |
| 60 | 60 | 60 | A 100 mA 0.1 sec. or less |
| Outdoor unit |
| P144 | 33.6/2 | – | 33.6/2 | 75 |
| 75 | 75 | 75 | A 100 mA 0.1 sec. or less | |
|
| P168 | 33.6/2 | – | 33.6/2 | 75 |
| 75 | 75 | 75 | A 100 mA 0.1 sec. or less | ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| P192 | 42.4/1 | – | 42.4/1 | 100 |
| 100 | 100 | 100 A 100 mA 0.1 sec. or less | |
|
|
|
| P204 | 42.4/1 | – | 42.4/1 | 100 |
| 100 | 100 | 100 A 100 mA 0.1 sec. or less | |
|
|
|
| P216 | 42.4/1 | – | 42.4/1 | 100 |
| 100 | 100 | 100 A 100 mA 0.1 sec. or less | |
|
|
|
| P234 | 42.4/1 | – | 42.4/1 | 100 |
| 100 | 100 | 100 A 100 mA 0.1 sec. or less | |
|
| Indoor unit |
| 0.41/22 | 0.41/22 | 0.41/22 | 15 |
| 15 | 15 | 20 | A 30 mA 0.1 sec. or less |
1.Use a separate power supply for the outdoor unit and indoor unit.
2.Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
3.The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops. Make sure the
4.Specific wiring requirements should adhere to the wiring regulations of the region.
5.Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example, use wiring such as YZW.
6.A switch with at least 3 mm [1/8in] contact separation in each pole shall be provided by the Air conditioner installation.
Warning:
•Be sure to use specified wires to connect so that no external force is imparted to terminal connections. If connections are not fixed firmly, it may cause heating or fire.
•Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Caution:
•A breaker for current leakage must be attached to the power supply. If no earth leakage breaker is installed, it may cause an electric shock.
•Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire.
11. Test run
11.1. The following phenomena do not represent trouble (emergency)
Phenomenon | Display of remote controller | Cause |
Indoor unit does not the perform cooling (heat- | “Cooling (heating)” flashes | When another indoor unit is performing the heating (cooling) operation, the cool- |
ing) operation. |
| ing (heating) operation is not performed. |
The auto vane runs freely. | Normal display | Because of the control operation of auto vane, it may change over to horizontal |
|
| blow automatically from the downward blow in cooling in case the downward |
|
| blow operation has been continued for 1 hour. At defrosting in heating, hot adjust- |
|
| ing and thermostat OFF, it automatically changes over to horizontal blow. |
Fan setting changes during heating. | Normal display | |
|
| Light air automatically changes over to set value by time or piping temperature at |
|
| thermostat ON. |
Fan stops during heating operation. | Defrost display | The fan is to stop during defrosting. |
|
|
|
Fan does not stop while operation has been | No lighting | Fan is to run for 1 minute after stopping to exhaust residual heat (only in heating). |
stopped. |
|
|
|
|
|
No setting of fan while start SW has been | Heat ready | Ultra |
turned on. |
| becomes 35°C [95°F], low speed operation for 2 minutes thereafter, and then set |
|
| notch is commenced. (Hot adjust control) |
Outdoor unit does not operate by turning | Normal display | When the outdoor unit is being cooled and the refrigerant is resting, warming up |
switch on. |
| operation is performed for at least 30 minutes to warm the compressor (only |
|
| P72). |
|
| During this time, only the fan operates. |
Indoor unit remote controller shows “HO” or | “HO” or “PLEASE WAIT” flashes | System is being driven. |
“PLEASE WAIT” indicator for about five min- |
| Operate remote controller again after “HO” or “PLEASE WAIT” disappear. |
utes when turning ON universal power supply. |
|
|
|
|
|
Drain pump does not stop while unit has been | Light out | After a stop of cooling operation, unit continues to operate drain pump for three |
stopped. |
| minutes and then stops it. |
Drain pump continues to operate while unit |
| Unit continues to operate drain pump if drainage is generated, even during a |
has been stopped. |
| stop. |
|
|
|
14