Monessen Hearth SWB400I Installation Preparation, Single Story Installation With Attic Space

Models: SWB400I

1 40
Download 40 pages 42.07 Kb
Page 9
Image 9
SINGLE STORY INSTALLATION WITH ATTIC SPACE

INSTALLATION PREPARATION

FIGURE 7

SINGLE STORY INSTALLATION WITH ATTIC SPACE

NOTICE:

Chimney must be correct height above the roof or other obstruction for safety and for proper draft operation. The chimney must be at least 3 feet

SC CHIMNEY CAP

STORM COLLAR (INCLUDED WITH CAP)

FLASHING (612 OR 1212)

ATTIC SPACE

FLUE OUTLET HEIGHT

3 FT. MIN. HEIGHT, AND 2 FT. MIN. ABOVE ANY POINT WITHIN 10 FEET OF CHIMNEY.

SEE TABLE 1 FOR

ROOF OPENING

SIZE

higher than the highest point where it passes through the roof and at least 2 feet higher than the highest part of the roof or structure that is within 10 feet of the chimney, measured horizontally. See Figures 7, 9, and 14.

16FT.

MIN.

SF FIRESTOP SPACER (1 3/4" AIR SPACE CLEARENCE TO COMBUSTIBLES)

14 1/2" SQUARE OPENING IN JOIST

2" MIN. CLEARENCE

FIGURE 9

TO COMBUSTIBLES

 

MULTIPLE STORY INSTALLATION

 

SC CHIMNEY CAP

 

FLUE OUTLET HEIGHT

FIGURE 8

NOTICE: PREFERRED LOCATION

16FT. POOR LOCATION

STORM COLLAR (INCLUDED WITH CAP) *86 FT. MAX.

FLASHING (612 OR 1212)

ATTIC SPACE

14 1/2" SQUARE HOLE IN JOIST (1 3/4" AIR SPACE CLEARANCE TO COMBUSTIBLES)

*86 FT. MAX.

INSTALLATION HEIGHT

2" MIN. CLEARANCE

TO COMBUSTIBLES Manual backgroundManual background (TYPICAL ALL AROUND.)

14 1/2" SQUARE HOLE IN JOIST (1 3/4" AIR SPACE CLEARANCE TO COMBUSTIBLES)

3 FT. MIN. HEIGHT, AND 2 FT. MIN. ABOVE ANY POINT WITHIN 10 FEET OF CHIMNEY.

SEE TABLE

1 FOR ROOF OPENING SIZE

SF FIRESTOP

SPACER

THIRD FLOOR AREA

SF FIRESTOP

SPACER

SECOND FLOOR AREA

Manual backgroundManual background SF FIRESTOP

SPACER

FIRST FLOOR AREA

*: SCS CHIMNEY SUPPORT REQUIRED EVERY 30 FEET OF INSTALLATION HEIGHT.

9

53D9033. Rev 1 03/03

Page 9
Image 9
Monessen Hearth SWB400I instruction manual Installation Preparation, Single Story Installation With Attic Space, 16FT MIN