Monessen Hearth SWB400I instruction manual Floor Protection

Models: SWB400I

1 40
Download 40 pages 42.07 Kb
Page 10
Image 10
FLOOR PROTECTION

FLOOR PROTECTION

If this fireplace is installed on a combustible floor, the floor area 16 inches in front of, and 8 inches either side of the fireplace opening must be protected by an insulating noncombustible hearth extension. This hearth extension may be either minimum 6-inch thick stone or brick as shown by Figure 10, a H1652 Hearth Extension Kit or a locally constructed hearth equivalent to the H1652.

The insulation used in the H1652 hearth extension has a thermal conductivity (K Factor) of .43. If you do construct a hearth extension equivalent to the H1652, be sure the insulation you use has enough compressive strength to support the weight of the covering materials and persons standing on it, and insulating qualities equal to or better than the ˚" covering provided by the H1652.

FIGURE 10

8"

MIN.

Manual background16"

MIN.

8"

MIN.

Manual background16"

MIN.

6" Manual background

MIN.

BRICK OR STONE

HEARTH EXTENSION

(52" LONG MIN.)

FIREPLACE

HEARTH

FIREPLACE

HEARTH

PLATFORM (PLATFORM MAY

EXTEND UNDER HEARTH

EXTENSION IF DESIRED.)

DO NOT PLACE HEARTH

MATERIALS ABOVE OPENING

OF FIREPLACE.

METAL SAFETY STRIP

ALTERNATE BRICK OR STONE HEARTH EXTENSION SHOWN WITHOUT THE OPTIONAL MLK36 LOUVER KIT INSTALLED ON THE FIREPLACE.

6" Manual background

MIN.

BRICK OR STONE HEARTH EXTENSION

Manual backgroundDO NOT PLACE HEARTH MATERIAL Manual background ABOVE OPENING OF FIREPLACE.

METAL SAFETY STRIP

(52" LONG MIN.)

8"

MIN.

Manual background16"

FIREPLACE

HEARTH

ALTERNATE BRICK OR STONE HEARTH EXTENSION SHOWN WITH THE OPTIONAL MLK36 LOUVER KIT INSTALLED ON THE FIREPLACE.

MIN.

6" Manual background

MIN.

BRICK OR STONE HEARTH EXTENSION

(52" LONG MIN.)

PLATFORM (PLATFORM MAY

EXTEND UNDER HEARTH

EXTENSION IF DESIRED.)

METAL SAFETY STRIP

DO NOT BLOCK ANY LOUVERED OPENINGS

10

53D9033. Rev 1 03/03

Page 10
Image 10
Monessen Hearth SWB400I instruction manual Floor Protection