Installing Top Housing or Termination

WR / WC Series Woodburning Fireplace

Installing Top Housing or Termination

Follow the installation instructions provided with the chimney termination you have selected.

Installing Chimney In a Chase

Refer to Page 5, Figure 5 for an illustration of a typical chase installation.

CAUTION: Treatment of firestop spacers and construc- tion of chase may vary with type of building. These instructions are not a substitute for local building codes. You must check your local building codes to determine specific requirements for your city or state. NOTE:

Air Space Clearances

Combustible framing material MUST NOT penetrate AIR SPACE (shaded areas).

156O" Installing Chimney In a Chase

Standoff

1/2" air space to sides

Other building materials may be required in addition to Firestop Spacers.

Finishing

CAUTION: All joints between the finished wall and the fireplace surround (top/sides) must be sealed with noncombustible material to prevent cold air leakage into the room. Only noncombustible material may be applied to the facing of the fireplace surround. (Black painted area) (Fig. 20)

Finish Wall

Finish the wall with material of your choice. Do not install a combustible mantel shelf less than 12" (305

mm) from the top of the fireplace opening for radiant

models and 12" (305 mm) from top of grille opening

for circulating models. Do not install a mantel face

plate less than 6" (159 mm) from top of fireplace

opening for radiant models and 6" (159 mm) from

top of grille opening for circulating models. (Fig.

22) If a combustible material is used below a flat man-

tel shelf, consult your local building codes for minimum

clearance from top of fireplace opening to bottom of

Front View

Wall

Shield

Only noncombustible material may be applied as facing to the black fireplace surround.

Side View

Air Space Clearances Firestop

1/2" Air Space to Back

1/2" Air Space to Sides

0" Clearance to Floor

Hearth

Extension

FP559

mantel shelf.

All joints (top, bottom and sides) where wall or deco- rative facing material meets fireplace surround must be completely sealed with a noncombustible material. (Figs. 21 and 22)

NOTE: No side wall protection is required for fireplaces installed at 45° to two (2) side walls (corner installation).

Often a decorative surround or vertical portion of the mantel is desired. If this is constructed of any combus- tible material it must be within the safe zone indicated in Figure 23.

Fig. 20 Minimum clearances to combustibles.

14

20014528

Page 14
Image 14