DCA-125SSJU SERIES — LOAD APPLICATION

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage and frequency requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

If wattage is not given on the equipment's

NOTE name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 4 below when connecting loads.

Table 4. Power Factor by Load

Type of Load

Power Factor

 

 

Single-phase induction motors

0.4 - 0.75

 

 

Electric heaters, incandescent

1.0

lamps

 

 

 

Fluorescent lamps, mecury lamps

0.4 - 0.9

 

 

Electronic devices, communication

1.0

equipment

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

Motors and motor-driven

NOTEequipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 5.

zWhen connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

zWhen connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

zWhen connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

Table 5. Cable Selection (60 Hz, Single Phase Operation)

Current in

Load In Watts

 

 

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

 

 

 

Amperes

At 120

At 240

#10 Wire

 

#12 Wire

#14 Wire

 

#16 Wire

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

 

600

ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

 

 

5

600

1200

500

ft.

 

300

ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

 

 

7.5

900

1800

350

ft.

 

200

ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

 

10

1200

2400

250

ft.

 

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

 

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

 

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION:

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious injury or death may result without this transfer switch.

If 3Ø load (kVA) is not given on the equipment nameplate,

NOTEapproximate 3Ø load output maybedeterminedbymultiplying voltage by amperage by 1.732.

DCA-125SSJU SERIES (STANDARD)— PARTS AND OPERATION MANUAL— REV. #4 (06/03/03) — PAGE 31

Page 31
Image 31
Multiquip manual DCA-125SSJU Series Load Application, Single Phase Load, Three Phase Load

DCA-125SSJU specifications

The Multiquip DCA-125SSJU is a robust and reliable diesel generator that stands out in the construction and rental markets. Designed to provide consistent power, this generator is ideal for various applications ranging from industrial construction sites to outdoor events. The DCA-125SSJU boasts a powerful 125 kVA output, making it suitable for both small and large power needs.

One of the prominent features of the DCA-125SSJU is its advanced engine technology. It is powered by a reliable and fuel-efficient Yanmar diesel engine. This engine not only ensures longevity but also optimizes fuel consumption, allowing operators to save on running costs without compromising performance. With a robust design, the Yanmar engine guarantees excellent cold start capability, making it dependable even under challenging weather conditions.

The generator's sound attenuation is also noteworthy. Encased in a sound-attenuated enclosure, the DCA-125SSJU operates at a noise level that makes it suitable for use in residential areas or environments with strict noise regulations. This feature enhances the generator's versatility, as it can be employed in various settings without disturbing nearby activities.

Multiquip has incorporated several safety features into the DCA-125SSJU, including automatic shutdown systems that activate in the event of low oil pressure or overheating. This proactive approach helps safeguard the engine and prolongs its lifespan. Additionally, the generator is equipped with a heavy-duty, weatherproof frame, ensuring durability and protection against the elements.

User-friendly control features make the DCA-125SSJU easy to operate. The generator includes an intuitive digital control panel that provides essential information such as voltage output, frequency, and run time. This accessibility allows operators to monitor performance and adjust settings as necessary.

Portability is another significant advantage of the DCA-125SSJU. With easily transportable dimensions, it can be efficiently moved to various job sites. Its sturdy wheels and lifting points further enhance mobility, making it a practical solution for temporary power needs.

In summary, the Multiquip DCA-125SSJU is a high-performance diesel generator, combining power, efficiency, and portability with advanced technology and user-friendly features. Its reliability and versatility make it an excellent choice for contractors, event organizers, and anyone in need of dependable power supply. Whether facing the demands of a construction site or hosting an outdoor function, the DCA-125SSJU ensures you’ll never be left in the dark.