DCA-15SPXU4 — GENERATOR START-UP PROCEDURE
Before Starting
CAUTION - LETHAL EXHAUST HAZARD
The engine's exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating.
Direct exhaust away from nearby personnel.
WARNING - STARTINGTHE GENERATOR
NEVER! manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.
1.Place the main, G.F.C.I., and aux. circuit breakers (Figure 25) in the OFF position prior to starting the engine.
Figure 25. Main, GFCI, and Auxillary
Circuit Breakers (OFF)
2.Connect the load to the receptacles or the output terminal lugs as shown in Figure 11. These load connection points can be found on the output terminal panel and the output terminal panel’s hard wire hookup panel.
3.Tighten terminal nuts securely to prevent load wires from slipping out.
4.Close all engine enclosure doors (Figure 26).
Start-up Procedure
1.Set the Speed Control Switch to the START/IDLE position (Figure 27).
Figure 27. Speed Control Switch (START/IDLE)
2.Insert the ignition key into the ignition switch. Turn the key clockwise to the
RUN |
| T | ||
PRE | RUN | |||
PRE | ||||
| ||||
STOP |
| STOP | ||
START | START | |||
|
| |||
| A |
| B |
Figure 28. Ignition Switch
3.Once the engine starts, let it engine run for
4.The generator's frequency meter (Figure 29) should be
displaying the 60 cycle output frequency in HERTZ.