Multiquip operation manual DCA-20SPX - SETUP, Circuit Breakers, Lubrication Oil, Fuel Check

Models: DCA-20SPX

1 84
Download 84 pages 40.15 Kb
Page 31
Image 31
Circuit Breakers

Circuit Breakers

To protect the generator from an overload, a 3-pole, 90 amp, main circuit breaker is provided to protect the U,O, and V OutputTerminals from overload. In addition two single-pole, 20 amp GFCI circuit breakers are provided to protect the GFCI receptacles from overload. Two 50 amp load circuit breakers have also been provided to protect the auxiliary receptacles from overload. Make sure to switch ALL circuit breakers to the OFF position prior to starting the engine.

Lubrication Oil

Fill the engine crankcase with lubricating oil through the filler hole, but DO NOT overfill. Make sure the generator is level. and verify that the oil level is maintained between the two notches (Figure 20) on the dipstick. See Table 8 for proper selection of engine oil.

DCA-20SPX — SETUP

Fuel Check

DANGER - EXPLOSION/FIRE HAZARDS

Fuel spillage on a hot engine can cause a fire or explosion. If fuel spillage occurs, wipe up the spilled fuel completely to prevent fire hazards. NEVER smoke around or near the generator.

Refilling the Fuel System

CAUTION - REFUELINGTHE GENERATOR

ONLY properly trained personel who have read and understand this section should refill the fuel tank system.

Figure 20. Engine Oil Dipstick

When checking the engine oil, be sure to check if the oil is clean. If the oil is not clean, drain the oil by removing the oil drain plug, and refill with the specified amount of oil as outlined in the Isuzu Engine Owner's Manual. Oil should be warm before draining.

Other types of motor oils may be substituted if they meet the following requirements:

API Service Classification CC/SC

API Service Classification CC/SD

API Service Classification CC/SE

API Service Classification CC/SF

Table 8. Recommended Motor Oil

F

C

OIL: SAE

 

12250

10440

8630

6820

5010

320 -14 -10 -4 -20 -22 -30 -40 -40

10W40

30

 

ARCTICOIL

5W30

10W/40

15W30

10W30

10W

20W40

This generator has an internal fuel tank located inside the trailer frame and may also be equipped with an optional environmental fuel tank (Figure 21). ALWAYS fill the fuel tanks with clean fresh #2 diesel fuel. DO NOT fill the fuel tanks beyond their capacities.

Pay attention to the fuel tank capacity when replenishing fuel.The fuel tank cap must be closed tightly after filling. Handle fuel in a safety container. If the container does not have a spout, use a funnel. Wipe up any spilled fuel immediately.

Figure 21. Internal Fuel Tank System

DCA-20SPX— OPERATION AND PARTS MANUAL — REV. #2 (04/14/10) — PAGE 31

Page 31
Image 31