Multiquip DCA-800SSK - GENERATOR OUTPUTS, Generator OutputVoltages, Voltage Change-Over Board

Models: DCA-800SSK

1 120
Download 120 pages 57.25 Kb
Page 36
Image 36
DCA-800SSK — GENERATOR OUTPUTS

DCA-800SSK — GENERATOR OUTPUTS

Generator OutputVoltages

A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by apply- ing jumpers (6) to the voltage change-over board (Figure 15). To obtain some of the voltages as listed in Table 7 (see below) will require a fine adjustment using the voltage regu- lator (VR) control knob located on the control panel.

Voltage Change-Over Board

The voltage change-over board (Figure 15) is located on the control box, behind the generator control panel. This board has been provided for ease of voltage selection.

Generator Amperage

Tables 8 and 9 describe the generator’s current output capa- bility for both 1Ø-phase and 3Ø phase applications.

Table 8. Generator Ampere Ratings — 1Ø

KW

139V

240V

277V

480V

 

 

 

 

 

40

208

120

104

60

100

519

301

261

150

 

 

 

 

 

160

831

481

417

241

 

 

 

 

 

220

1,142

662

573

331

 

 

 

 

 

280

1,454

842

730

421

 

 

 

 

 

340

1,765

1,022

886

511

 

 

 

 

 

400

2,077

1,203

1,042

601

 

 

 

 

 

460

2,388

1,383

1,199

692

 

 

 

 

 

520

2,700

1,564

1,355

782

580

3,011

1,744

1,511

872

 

 

 

 

 

640

3,323

1,925

1,667

962

 

 

 

 

 

Figure 15. Voltage Change-Over Board 240V Configuration

CAUTION - CHANGING JUMPER PLATES

NEVER attempt to place jumper plates on the voltage change-over board while the generator is in operation. There exists the possibility of electrocution, electrical shock or burn, which can cause severe bodily harm or even death!

Table 7. Generator Available Voltages

Three-Phase 208V

220V

240V

416V

440V

480V

Table 9. Generator Ampere Ratings — 3Ø

KW

240V
480V

40

120

60

 

 

 

100

301

150

 

 

 

160

481

241

 

 

 

220

662

331

 

 

 

280

842

421

 

 

 

340

1,022

511

 

 

 

400

1,203

601

 

 

 

460

1,383

692

 

 

 

520

1,564

782

 

 

 

580

1,744

872

 

 

 

640

1,925

962

 

 

 

Single-Phase

120V 127V 139V 240V 254V 277V

PAGE 36 — DCA-800SSK (STD) — OPERATION AND PARTS MANUAL — REV. #4 (06/03/10)