DCA-600SSK — GENERATOR SHUT-DOWN PROCEDURE
Engine Shutdown Ignition Key (Up to S/N 3699247)
To shutdown the generator use the following procedure:
1.Place both the MAIN, GFCI and LOAD circuit breakers (Figure 69) to the "OFF position".
Figure 69. Main, Aux. and GFCI
Circuit Breakers (OFF)
2.Place the throttle control (Figure 70) in the “LOW”position.
Figure 70. Engine Throttle Control
Engine Shutdown Controller (S/N 3698617~)
To shutdown the generator use the following procedure:
1.Place both the MAIN, GFCI and LOAD circuit breakers as shown in Figure 67 to the "OFF position".
2.Place the engine speed switch in the “LOW ” position (Figure 73).
Figure 73. Engine Speed Switch (High)
3.Let the engine cool by running it for
4.Place the
Figure 74. Off/Manual Auto Switch (AUTO)
3.Let the engine cool by running it for
4.Place the ignition key (Figure 71) in the “STOP” position.
Figure 71. Ignition Key Switch (STOP position)
5. Remove all loads from the generator.
Emergency Shutdown Procedure
1.PUSH inward the emergency stop button located on the engine operating panel (Figure 72) to turn off the generator in the event of an emergency. This button is located on either Engine Operating Panel.
Figure 72. Emergency Stop Button
5.Verify that the all status LED on the MPEC display are "OFF" (not lit).
6.Remove all loads from the generator.
WARNING - EMERGENCY STOP SWITCH
NEVER stop the engine suddenly except in an emergency. DO NOT use the emergency stop switch as a method of shutting down the generator. This switch is ONLY to be used in the event of an emergency.
To disengage the emergency stop function, pull the emergency stop button outward to its
NOTEoriginal position.This will allow the generator to operate normally. Rememberthe generator will not start if the emergency stop button is engaged.
PAGE 50 —