GENERATOR SHUT-DOWN PROCEDURES

12.The coolant temperature gauge (Figure 50) will indicate the coolant temperature. Under normal operating conditions the coolant temperature should be between 167°~203°F (75°~95°C) (Green Zone).

WARNING

NEVER stop the engine suddenly except in an emergency.

Normal Shutdown Procedure

Figure 50. Coolant Temperature Gauge

13.The tachometer gauge (Figure 51) will indicate the speed of the engine when the generator is operating. Under normal operating conditions this speed is approximately 1800 RPM’s.

To shutdown the generator, use the following procedure:

1.Place both the MAIN, GFCI and LOAD circuit breakers as shown in Figure 54 to the OFF position..

Figure 51. Engine Tachometer Gauge

14.Place the main, GFCI, and aux. circuit breakers in the ON position (Figure 52).

Figure 52. Main, Aux. and GFCI

Circuit Breakers (ON)

15.Observe the generator’s ammeter (Figure 53) and verify it reads the anticipated amount of current with respect to the load. The ammeter will only display a current reading if a load is in use.

Figure 53. Ammeter (Load)

Figure 54. Main, GFCI and Load

Circuit Breakers Off

2.Place the engine speed switch (Figure 55) in the “LOW” (down) position..

Figure 55. Ignition Switch (Normal)

3.Let the engine cool by running it at low speed for 3-5 minutes with no load applied.

4.Place the MPEC Control Switch (Figure 56) to the

OFF/RESET position.

Figure 56. MPEC Control Switch (Off/Reset)

5.Verify that all status LEDs on the MPEC display are OFF (not lit).

6.Remove all loads from the generator.

7.Inspect entire generator for any damage or loosening of components that may have occurred during operation.

Emergency Shutdown Procedure

16.The generator will run until manually stopped or an abnormal condition occurs.

1.Place the MPEC Control Switch (Figure 56) in the

OFF/RESET position.

page 36 — DCA125USI3CAN 60 hz Generator • operation and parts manual — rev. #2 (09/24/13)

Page 36