DCA-180SSK — OUTPUTTERMINAL PANEL OVERVIEW

OUTPUTTERMINAL FAMILIARIZATION

The “Output Terminal Panel” is provided with the following:

Two 120V GFCI receptacles, 20 amp

Three 240/139V output receptacles, 50 amp

Two 120V input receptacles, 20 amp (optional)

3 Load Circuit Breakers 265V @65 amps

2 Load GFCI Circuit Breakers 265V@ 20amps

Control Box

The “Control Box” is provided with the following:

Main Circuit Breaker 500 amps

Over-Current Relay

Output Terminal Panel

The Output Control Panel (See Figure 4) is located on the right hand side (left from control panel) of the generator. The UVW lugs are protected by a face plate cover that can be secured in the close position by a pad lock. (See Figure 11).

FIGURE 12. Output Terminal Cover

120 Volt Receptacle

Two GFCI Duplex Nema 5-20R (120V, 20 Amp) receptacle is provided on the output terminal. This receptacle can be used anytime the generator is in operation. The receptacle is controlled by the circuit breaker located on the control panel.

Pressing the reset button resets the receptacle after being tripped. Pressing the "Test Button" (See Figure 12) in the center of this receptacle will check the GFCI function. The receptacle should be tested at least once a month.

FIGURE 12. GFCI Test Button

Connecting Load

Loads can be connected to the generator by the UVWO Lugs or the convenience receptacles. (See figure 13). Make sure to read the operation manual before attempting to connect a load to the generator.

FIGURE 13. Connecting Load

Circuit Breakers

To protect the generator from an overload, a 3-pole, 500 amp, main circuit breaker is provided to protect the UVW output terminals from overload. In addition two single-pole, 20 amp GFCI circuit breakers are provided to protect the GFCI receptacles from overload.Three 50 amp load circuit breakers have also been provided to protect the load side of the generator from overload. Make sure to switch ALL circuit breakers to the "OFF" position prior to starting the engine.

Maximum Output

The entire load connected to the UVWO Lugs, all four slots in the duplex receptacles, and the must not exceed 158 kW in standby or 144 kW in prime output.

Twist Lock Dual Voltage Receptacles

Three CS-6369 auxiliary power receptacles have been provided to supply 208/120V. The voltage regulator knob on the control panel may need to be used to adjust the voltage to 208 or 416V.

Input Receptacles

Two 120 volt, 20 amp input receptacles are provided to supply power to accessories, such as the battery charger (optional) or jacket water heater (optional).

PAGE 34 — DCA-180SSK — PARTS AND OPERATION MANUAL — REV. #3 (06/11/09)

Page 34
Image 34
Multiquip DCA180SSK manual DCA-180SSK Outputterminal Panel Overview

DCA180SSK specifications

The Multiquip DCA180SSK is a powerful and versatile generator specifically designed for construction sites, events, and other demanding applications. This model boasts an impressive power output of 180 kVA, making it suitable for a wide range of electrical needs. Its reliable performance combined with advanced features makes it a preferred choice for professionals in various industries.

One of the standout characteristics of the DCA180SSK is its robust, diesel-powered engine. This generator is equipped with a reliable Yanmar diesel engine, known for its durability and efficiency. The engine not only ensures consistent power delivery but also meets stringent emission regulations, making it environmentally friendly. The unit features a fuel-efficient design capable of running for extended periods, which reduces the frequency of refueling and associated downtime.

The DCA180SSK generator is also engineered for ease of use. It incorporates a user-friendly control panel that provides clear visibility of operational parameters, including voltage output, frequency, and fuel levels. This intuitive interface allows operators to monitor the generator’s performance effortlessly.

Another significant technological advancement in the DCA180SSK is its advanced sound attenuation features. The generator is built within a durable, weather-protective enclosure that minimizes noise levels to enhance worksite safety and compliance with local regulations. This feature not only benefits job sites in urban environments but also improves working conditions for operators and workers alike.

Portability is another key attribute. The DCA180SSK is designed with a compact structure, making it easy to transport and position on-site. The addition of lifting points facilitates quick and safe relocation, while its rugged chassis ensures it can withstand the rigors of construction environments.

This generator also incorporates numerous safety features, including automatic shut-off protocols for low oil pressure and high temperature, enhancing operator safety and extending engine life. With its blend of technology, durability, and user-centric design, the Multiquip DCA180SSK generator provides dependable power for any demanding application, ensuring that work proceeds smoothly, efficiently, and safely.